HP 30 HP30 User Manual

Page 31

Advertising
background image

Chapter 2 - Operation

2-3

2.2.1

LCD Keypad Display



DRV

¢º

T/K 0.0 A

00 STP 0.00 Hz





Displays

Description

1) Parameter Group

Displays the parameter group. There are DRV, FU1, FU2, I/O, EXT, COM, APP groups.

2) Run/Stop Source

Displays the source of motor Run and Stop
K: Run/Stop using FWD, REV buttons on keypad
T: Run/Stop using control terminal input FX, RX
O: Run/Stop via option board

3) Frequency Setting
Source

Displays the source of command frequency setting
K: Frequency setting using keypad
V: Frequency setting using V1 (0 ~10V) or V1 + I terminal
I: Frequency setting using I (4 ~ 20mA) terminal
U: Up terminal input when Up/Down operation is selected
D: Down terminal input when Up/Down operation is selected
S: Stop status when Up/Down operation is selected
O: Frequency setting via Option board
X: Frequency setting via Sub board
J: Jog terminal input
1 ~ 8: Step frequency operation
* During Auto operation, 2) and 3) display the ‘sequence number/step’.

4) Output Current

Displays the Output Current during operation.

5) Parameter Code

Displays the code of a group. Use the ▲(Up), ▼(Down) key to move through 0~99 codes.

6) Operating Status

Displays the operation information.
STP: Stop Status
FWD: During Forward operation
REV: During Reverse operation
DCB: During DC Braking
LOP: Loss of Reference from Option Board (DPRAM fault)
LOR: Loss of Reference from Option Board (Communication network fault)
LOV: Loss of Analog Frequency Reference (V1: 0~10V)
LOI: Loss of Analog Frequency Reference (I: 4~20mA)
LOS: Loss of Reference from Sub-Board

7) Drive Output Frequency
Command Frequency

Displays the Output Frequency during run.
Displays the Command Frequency during stop.

2) Run/Stop Source

3) Frequency Setting Source

4) Output Current

7) Drive Output Frequency During Run,
Command Frequency During Stop

6) Operating Status

5) Parameter Code

1) Parameter group

Advertising