Chapter 6 - Parameter Description [DRV]

6-3

DRV-02: Deceleration Time






The inverter targets the FU2-70 when accelerating or
decelerating. When the FU2-70 is set to “Maximum
Frequency”, the acceleration time is the time taken by the
motor to reach FU1-20 from 0 Hz. The deceleration time is
the time taken by the motor to reach 0 Hz from FU1-20
[Maximum Frequency].

When the FU2-70 is set to ‘Delta Frequency’, the
acceleration and deceleration time is the time taken to
reach a targeted frequency (instead the maximum
frequency) from a frequency.

The acceleration and deceleration time can be changed to
a preset transient time via multi-function inputs. By setting
the multi-function inputs (P1, P2, P3) to ‘XCEL-L’, ‘XCEL-
M’, ‘XCEL-H’ respectively, the Accel and Decel time set in
I/O-25 to I/O-38 are applied according to the binary inputs
of the P1, P2, P3.






















➨ Note:

I/O-12 to I/O-14: Sets the terminal function of P1, P2,

P3 terminal inputs.

Code

LCD

display

Description

XCEL-

H

XCEL-

M

XCEL-

L

Factory

setting

DRV-

01

Acc time

Acc time 0

0

0

0

10 sec

DRV-

02

Dec time

Dec time 0

0

0

0

20 sec

I/O-25 ACC-1

Acc time 1

0

0

1

20 sec

I/O-26 DEC-1

Dec time 1

0

0

1

20 sec

I/O-27 ACC-2

Acc time 2

0

1

0

30 sec

I/O-28 DEC-2

Dec time 2

0

1

0

30 sec

I/O-29 ACC-3

Acc time 3

0

1

1

40 sec

I/O-30 DEC-3

Dec time 3

0

1

1

40 sec

I/O-31 ACC-4

Acc time 4

1

0

0

50 sec

I/O-32 DEC-4

Dec time 4

1

0

0

50 sec

I/O-33 ACC-5

Acc time 5

1

0

1

40 sec

I/O-34 DEC-5

Dec time 5

1

0

1

40 sec

I/O-35 ACC-6

Acc time 6

1

1

0

30 sec

I/O-36 DEC-6

Dec time 6

1

1

0

30 sec

I/O-37 ACC-7

Acc time 7

1

1

1

20 sec

I/O-38 DEC-7

Dec time 7

1

1

1

20 sec


FU2-71 [Accel/Decel time scale]

Set the Accel / Decel time unit.

Setting

Unit

Description

0 0.01

sec

Minimum 0 sec settable
Maximum 60 sec settable

1 0.1

sec

Minimum 0 sec settable
Maximum 600 sec settable
(Factory setting)

2 1

sec

Minimum 0 sec settable
Maximum 6000 sec settable*


* Up to 6000 sec setting is avaiable via LE-200 keypad.



DRV-03: Drive Mode (Run/Stop Method)






Select the source of run/stop command.

DRV

► Dec. time

02 20.0 sec

20.0

02

Factory Default:

20.0 sec

20.0

Related Functions: FU1-20 [Max freq]

FU2-70 [Reference freq. for Accel/Decel]

FU2-71 [Accel/Decel time scale]

I/O-12 to I/O-14 [Multi-function input

terminal P1, P2, P3]

I/O-25 to I/O-38 [Acc/Dec time for step

frequency]

FU2-70: Selects the frequency to be targeted for acceleration

and deceleration. [Max Freq, Delta Freq]

FU2-71: Selects the time scale. [0.01, 0.2, 1]

I/O-12 to I/O-14: Sets the terminal function of P1, P2, P3

terminal inputs.

I/O-25 to I/O-38: Presets the Accel/Decel time activated via

multifunction inputs (P1, P2, P3)

Output Frequency

Max. Freq.

Time

Acc. time

Dec. time

DRV

► Drive mode

03 Keypad

1

03

Factory Default:

Fx/Rx-1

1