HP 30 HP30 User Manual

Page 88

Advertising
background image

Chapter 6 - Parameter Description [DRV]

6-4

Setting Range

LCD 7-Seg

Description

Keypad

0

Run/Stop is controlled by Keypad.

Fx/Rx-1

1

Control Terminals FX, RX and 5G
control Run/Stop. (Method 1)

Fx/Rx-2

2

Control Terminals FX, RX and 5G

control Run/Stop. (Method 2)














[Drive Mode: ‘Fx/Rx-1’]














[Drive Mode: ‘Fx/Rx-2’]






DRV-04: Frequency or Torque Mode (Frequency /
Torque Setting Method)






* In Torque mode : LCD display: “Trque mode”

7 Segment: “04”

If the DRV-04 [Frequency or Torque Mode] is set to 2

(V1), 3 (I), 4 (V1+I), see the description of I/O-01~10
[Analog Voltage/Current input signal adjustment].

If FU2-39 is set to 4 (Sensorless_T) or 6

(Vector_TRQ), speed is displayed as the percent[%]

to the rated torque. Torque command is settable in

DRV-04 [Frequency or Torque Mode].

DRV-04 setting value is separately saved according

to which control mode (Speed or Torque) is selected
in FU2-39 [Control mode selection].


Setting Range

LCD 7-Seg

Description

Keypad-1 0

Frequency is set at DRV-00. The
frequency is changed by pressing

PROG

key and entered by pressing

ENT key.

The inverter does not output the changed
frequency until the

ENT key is pressed.

Keypad-2 1

Frequency is set at DRV-00. Press

PROG key and then by pressing the ▲,
▼ key, the inverter immediately outputs

the changed frequency. Pressing the

ENT key saves the changed frequency.

V1 2

Input the frequency reference (0-10V) to
the “V1” control terminal. Refer to the I/O-

01 to I/O-05 for scaling the signal.

I 3

Input the frequency reference (4~20mA)
to the “I” control terminal. Refer to the

I/O-06 to I/O-10 for scaling the signal.

V1+I 4

Input the frequency reference (0~10V,
4~20mA) to the “V1”,“I” control terminals.

The ‘V1’ signal overrides the ‘I’ signal.

Output Frequency

FX-CM

Time

ON

RX-CM

ON

Forward

Reverse

Forward Run

Reverse Run

Output Frequency

FX-CM

Time

ON

RX-CM

ON

Forward

Reverse

Run/Stop

Direction

DRV

► Freq mode*

04

Keypad-1

0

04

Factory Default:

Keypad-1 0

Advertising