Chapter 6 - Parameter Description [DRV]

6-5










[Freq Mode: ‘V1’]










[Freq Mode: ‘I’]











[Freq Mode: V1+’I’]






DRV-05 ~ DRV-07: Step Frequency 1 ~ 3
















The inverter outputs preset frequencies set in these codes
according to the multi-function terminals configured as
‘Speed-L’, ‘Speed-M’ and ‘Speed-H’. The output
frequencies are decided by the binary combination of P1,
P2, P3 configured in I/O-12 to I/O-17. Refer to the
following table for the preset frequency outputs.

Binary Combination of P1, P2, P3

Speed-L Speed-M Speed-H

Output

Frequency

Step Speed

0 0 0

DRV-00

Speed

0

1 0 0

DRV-05

Speed

1

0 1 0

DRV-06

Speed

2

1 1 0

DRV-07

Speed

3
















[Step Frequency Output]

Output Frequency

Analog Signal
Input (V1)

Freq. max

0V

10V

Reference Freq. Range

Output Frequency

Freq. Max

4mA

20mA

Reference Freq. Range

Analog Signal
Input (I)

Output Frequency

Freq. Max

0V+4mA

Reference Freq. Range

10V+20mA

Analog Signal
Input (‘V1+I’)

DRV

► Step freq-1

05 10.00 Hz

10.00

05

Factory Default:

10.00 Hz

10.00

DRV

► Step freq-2

06 20.00 Hz

20.00

06

Factory Default:

20.00 Hz

20.00

DRV

► Step freq-3

07 30.00 Hz

30.00

07

Factory Default:

30.00 Hz

30.00

P1-CM

ON

Output Frequency

Time

Time

P2-CM

ON

Time

P3-CM

Time

ON

Speed 3

Speed 0

Speed 2
Speed 1

Related functions: DRV-00 [Digital Command Frequency or

Command Torque ]

FU2~39 [Control Mode Selection]

I/O-01~10 [Analog Voltage/Current input
signal adjustment]