Chapter 8 - Troubleshooting & Maintenance


8-5

8.3 Troubleshooting

Condition

Check Point

The Motor Does Not
Rotate

1) Main circuit inspection:

☞

Is the input (line) voltage normal? (Is the LED in the inverter is lit?)

☞

Is the motor connected correctly?

2) Input signal inspection:

☞

Check the operating signal input to the inverter.

☞

Check the forward and the reverse signal input simultaneously to the inverter?

☞

Check the command frequency signal input to the inverter.

3) Parameter setting inspection:

☞

Is the reverse prevention (FU1-03) function set?

☞

Is the operation mode (FU1-01) set correctly?

☞

Is the command frequency set to 0?

4) Load inspection:

☞

Is the load too large or is the motor jammed? (Mechanical brake)

5) Other:

☞

Is the alarm displayed on the keypad or is the alarm LED lit? (STOP LED blinks)

The Motor Rotates
in Opposite
Directions

☞

Is the phase sequence of the output terminal U, V, W correct?

☞

Is the starting signal (forward/reverse) connected correctly?

The Difference
Between the
Rotating Speed and
the Reference is
Too Large

☞

Is the frequency reference signal correct? (Check the level of the input signal)

☞

Is the following parameter setting is correct?

Lower Limit Frequency (FU1-24), Upper Limit Frequency (FU1-25), Analog Frequency Gain (I/O-1~10)

☞

Is the input signal line influenced by external noise? (Use a shielded wire)

The Inverter Does
Not Accelerate or
Decelerate
Smoothly

☞

Is the acceleration/deceleration time is set too short a period of time?

☞

Is the load too large?

☞

Is the Torque Boost (FU1-27, 28) value is too high that the current limit function and the stall prevention

function do not operate?

The Motor Current
is Too High

☞

Is the load too large?

☞

Is the Torque Boost Value (manual) too high?

The Rotating Speed
Does Not Increase

☞

Is the Upper Limit Frequency (FU1-25) value correct?

☞

Is the load too large?

☞

Is the Torque Boost (FU1-27, 28) value too high that the stall prevention function (FU1-59, 60) does not

operate?

The Rotating Speed
Oscillates When the
Inverter is
Operating.

1) Load inspection:

☞

Is the load oscillating?

2) Input signal inspection:

☞

Is the frequency reference signal oscillating?

3) Other:

☞

Is the wiring too long when the inverter is using V/F control? (over 500m)