Chapter 5 - Parameter List

5-4

Keypad Display

Setting Range

Code

Description

LCD

7-Segment

LCD

7-Segment

Units

Factory

Default

Adj.

During

Run

Page

FU1-25 High Limit Frequency

F-limit Hi

25

FU1-24 to FU1-20

0.01 60.00 [Hz]

No

Manual 0

FU1-26

Manual/Auto Torque
Boost Selection

Torque boost

26

Auto 1

- Manual No

6-2

FU1-27

Torque Boost in Forward
Direction

Fwd boost

27

0 to 15 [%]

0.1

2.0 [%]

No

FU1-28

Torque Boost in Reverse
Direction

Rev boost

28

0 to 15 [%]

0.1

2.0 [%]

No

6-2

Linear 0

Square 1

FU1-29 Volts/Hz Pattern

V/F pattern

29

User V/F

2

- Linear No

6-2

FU1-30

15

User V/F – Frequency 1

User freq 1

30

0 to FU1-20

0.01 15.00 [Hz]

No

FU1-31 User V/F – Voltage 1

User volt 1

31

0 to 100 [%]

1

25 [%]

No

FU1-32 User V/F – Frequency 2

User freq 2

32

0 to FU1-20

0.01 30.00 [Hz]

No

FU1-33 User V/F – Voltage 2

User volt 2

33

0 to 100 [%]

1

50 [%]

No

FU1-34 User V/F – Frequency 3

User freq 3

34

0 to FU1-20

0.01 45.00 [Hz]

No

FU1-35 User V/F – Voltage 3

User volt 3

35

0 to 100 [%]

1

75 [%]

No

FU1-36 User V/F – Frequency 4

User freq 4

36

0 to FU1-20

0.01 60.00 [Hz]

No

FU1-37 User V/F – Voltage 4

User volt 4

37

0 to 100 [%]

1

100 [%]

No

6-2

FU1-38

Output Voltage
Adjustment

Volt control

38

40 to 110 [%]

0.1

100.0 [%]

No

6-2

FU1-39 Energy Save Level

Energy save

39

0 to 30 [%]

1

0 [%]

Yes

6-2

No 0

FU1-50

Electronic Thermal
Selection

ETH select

50

Yes 1

- No Yes

FU1-51

16

Electronic Thermal Level
for 1 Minute

ETH 1 min

51

FU1-52 to 200 [%]

1

150 [%]

Yes

FU1-52

Electronic Thermal Level
for Continuous

ETH cont

52

50 to FU1-51

1

100 [%]

Yes

Self-cool 0

FU1-53

Electronic Thermal
Characteristic Selection
(Motor Type)

Motor type

53

Forced-cool 1

- Self-cool Yes

6-2

FU1-54 Overload Warning Level

OL level

54

30 to 150 [%]

1

150 [%]

Yes

FU1-55

Overload Warning Hold
Time

OL time

55

0 to 30 [sec]

0.1

10.0 [sec]

Yes

6-2

No 0

FU1-56 Overload Trip Selection

OLT select

56

Yes 1

- Yes Yes

FU1-57 Overload Trip Level

OLT level

57

30 to 150 [%]

1

180 [%]

Yes

FU1-58 Overload Trip Delay Time

OLT time

58

0 to 60 [sec]

1

60.0 [sec]

Yes

6-2

FU1-59

Stall Prevention Mode
Selection

Stall prev.

59

000 to 111

(Bit Set)

bit 000 No

FU1-60 Stall Prevention Level

Stall level

60

30 to 250 [%]

1

180 [%]

No

6-2

15

Code FU1-30 through FU1-37 appears only when FU1-29 is set to ‘User V/F’.

16

Code FU1-51 through FU1-53 appears only when FU1-50 is set to ‘Yes’.

Advertising