HP 30 HP30 User Manual

Page 112

Advertising
background image

Chapter 6 - Parameter Description [FU2]

6-20

This function is used to allow the inverter to reset itself for
a selected number of times after a fault has occurred. The
inverter can restart itself automatically when a fault occurs.
To use the speed search function during auto restarting set
FU2-22 to ‘xx1x’. See FU2-22 ~ FU2-25.
When an under voltage (LV) fault, inverter disable (BX) or
Arm short occurs, the drive does not restart automatically.















Note: Inverter decreases the retry number by one as a fault

occurs. When restarted without a fault during 30 seconds,
the inverter increases the retry number by one.


FU2-28: Speed search hold time



The inverter starts speed search function after the preset
time t1 elapses. Set the desired time for inverter to restart
the previous operation using Speed search function.
Speed search function [FU2-22] is activated automatically
during exchanging function.

Code

Keypad
display

Description

Factory
setting

Setting
Range

FU2-28 SS blk time

Speed search
hold time
during speed
search

1 sec

0 ~ 60
sec





























Note: This parameter is not valid when low voltage (LV)

fault or instant power loss (within 15msec) occurs.

FU2-30: Rated Motor Selection
FU2-31: Number of Motor Pole
FU2-32: Rated Motor Slip
FU2-33: Rated Motor Current
FU2-34: No Load Motor Current
FU2-36: Motor Efficiency
FU2-37: Load Inertia


If you do not set these values, inverter will use its default
values.






This parameter sets the motor capacity. Other motor
related parameters are changed automatically according to

Output Frequency

Time

1

st

Fault

2

nd

Fault

Restart with

Speed Search

Restart with

Speed Search

t

t

t: FU2-27

Input power[v]

Time [sec]

Motor speed [rpm]

t1 t2 t3

t1 : Ssearch wait time

t2 : Ssearch Accel time
t3 : Ssearch Decel time

Output vtg [V]

Time [sec]

Time [sec]

FU2

►Motor select

30 0.75kW

0

30

Factory Default:

0.75 kW

0

(This value is set according to the model number before shipping)

FU2

► SS blk time

28 1.0 sec

1.0

28

Factory Default:

1.0 sec

1. 0

Advertising