HP 30 HP30 User Manual

Page 129

Advertising
background image

Chapter 6 - Parameter Description [I/O]

6-37

The following table shows the selection in I/O-48.

Setting Range
LCD 7-Seg

Description

None

0

Continuous operating after loss of
frequency reference.

FreeRun

1

Inverter cuts off its output after
determining loss of frequency reference.

Stop

2

Inverter stops by its Decel pattern and

Decel time after determining loss of
frequency reference.


I/O-49 [Time out] sets the waiting time before determining
the loss of reference signal. Inverter waits to determine the
loss of a reference signal until times out.

Note: I/O-48 and I/O-49 also apply when DRV-04 is set to

‘Keypad-1’ or ‘Keypad-2’ for determining the loss of
command frequency.







I/O-12: Multi-function Input Terminal ‘P1’ Define
I/O-13: Multi-function Input Terminal ‘P2’ Define
I/O-14: Multi-function Input Terminal ‘P3’ Define
















Multi-function input terminals can be defined for many
different applications. The following table shows the
various definitions for them.

Setting Range

LCD 7-Seg

Description

Speed-L

0

Multi-step speed - Low

Speed-M

1

Multi-step speed - Mid

Speed-H

2

Multi-step speed - High

XCEL-L

3

Multi-accel/decel - Low

XCEL-M

4

Multi-accel/decel - Mid

XCEL-H

5

Multi-accel/decel - High

Dc-brake

6

DC injection braking during stop

2nd

Func

7

Exchange to 2

nd

functions

Exchange

8

Exchange to commercial power line

-Reserved-

9

Reserved for future use

Up

10

Up drive

Down

11

Down drive

3-Wire

12

3 wire operation

Ext Trip-A

13

External trip A

Ext Trip-B

14

External trip B

iTerm Clear

15

Used for PID control

Open-loop

16

Exchange between PID mode and

V/F mode

Main-drive

17

Exchange between Option and
Inverter

Analog hold

18

Hold the analog input signal

XCEL stop

19

Disable accel and decel

P Gain2

20

Used for PID control

SEQ-L

21

Sequence operation - Low

SEQ-M

22

Sequence operation - Mid

SEQ-H

23

Sequence operation - High

Manual

24

Exchange between Sequence
operation and Manual operation

Go step

25

Triggering Sequence operation
(Auto-B)

Hold step

26

Hold last step (Auto-A)

Trv Off.Lo

27

Trv Off.Hi

28

Used for Traverse Operation

Interlock1

29

Interlock2

30

Interlock3

31

Interlock4

32

Used for MMC operation


[Speed-L, Speed-M, Speed-H]
By setting P1, P2, P3 terminals to ‘Speed-L’, ‘Speed-M’
and ‘Speed-H’ respectively, inverter can operate at the
preset frequency set in DRV-05 ~ DRV-07 and I/O-20 ~
I/O-24.

The step frequencies are determined by the combination of
P1, P2 and P3 terminals as shown in the following table.




Related Functions: DRV-04 [Frequency Mode]

I/O-02 [V1 Input Minimum Voltage]

I/O-07 [I Input Minimum Current]

I/O-48 [Lost command]

I/O-49

[Time out]

I/O

► P1 dedine

12 Speed-L

0

12

Factory Default:

Speed-L

0

I/O

► P2 dedine

13 Speed-M

1

13

Factory Default:

Speed-M

1

I/O

► P3 dedine

14 Speed-H

2

14

Factory Default:

Speed-H

2

2

14