Chapter 6 - Parameter description [FU1]

6-19

Motor Current].













[Overload Warning]







FU1-56: Overload Trip Selection
FU1-57: Overload Trip Level
FU1-58: Overload Trip Delay Time
















Inverter cuts off its output and displays fault message
when the output current persists over the FU1-57
[Overload Trip Level] for the time of FU1-58 [Overload Trip
Time]. This function protects the inverter and motor from
abnormal load conditions.

Note: The set value is the percentage of FU2-33 [Rated

Motor Current].
















[Overload Trip Operation]





FU1-59: Stall Prevention Mode Selection (Bit set)
FU1-60: Stall Prevention Level






This bit set parameter follows the conventions used in I/O-
15 and I/O-16 to show the ON (bit set) status.






This function is used to prevent the motor from stalling by
reducing the inverter output frequency until the motor
current decreases below the stall prevention level. This
function can be selected for each mode of acceleration,
steady speed, and deceleration via bit combination.

t1: FU1-55 [Overload Warning Time]

Output Current

Time

Time

FU1-54

[OL Level]

FU1-54

[OL Level]

AXA-AXC

ON

t1

t1

Related Functions: FU2-33 [Rated Motor Current]

I/O-44 [Multi-function Auxiliary Contact

Output]

FU1

► OLT select

56 --- Yes ---

1

56

Factory Default:

Yes

1

FU1

► OLT level

57 180 %

180

57

Factory Default:

180 %

180

FU1

► OLT time

58 60.0 sec

60.0

58

Factory Default:

60.0 sec

60.0

Output Current

Time

Time

FU1-57

[OLT Level]

FU1-57

[OLT Level]

Output Frequency

FU1- 58 [OLT Time]

Overload Trip

Related Functions: FU2-33 [Rated Motor Current]

FU1

► Stall prev.

59 000

000

59

Factory Default: 000

000

FU1

► Stall level

60 180 %

180

60

Factory Default:

180 %

180