Chapter 6 - Parameter Description [FU2]

6-18





















[Power ON Start: ‘No’]






[Power ON Start: ‘Yes’]

Note: In case of using ‘Power ON Start’ to ‘Yes’, make sure

to utilize appropriate warning notices to minimize the
potential for injury or equipment damage.




FU2-21: Restart After Fault Reset






If FU2-21 is set to ‘Yes’, inverter will restart after the RST
(reset) terminal has been reset a fault.
If FU2-21 is set to ‘No’, restart the inverter by cycling the
FX or RX terminal to CM terminal after the fault has been

reset. If the motor is rotating by inertia at the time power is
restored, the inverter may trip. To avoid this trip, use
‘Speed Search’ function by setting FU2-22 to ‘xx1x’.











[Reset restart: ‘No’]












[Reset restart: ‘Yes’]


Note: In case of using ‘Reset Restart’ to ‘Yes’, make sure to

utilize appropriate warning notices to minimize the potential
for injury or equipment damage.




FU2-22: Speed Search Selection (Bit Set)
FU2-23: Current Limit Level During Speed Search
FU2-24: P Gain During Speed Search
FU2-25: I Gain During Speed Search






Input Power

Time

FX-CM

ON

Time

ON

No Effect

Start

Power On

Output Frequency

Time

Input Power

Time

FX-CM

ON

Time

Start

Power On

Output Frequency

Time

FU2

► RST restart

21 --- No ---

0

21

Factory Default:

No

0

Output Frequency

Time

FX-CM

ON

Time

RST-CM

ON

Time

ON

No Effect

Start

Tripped

Output Frequency

Time

FX-CM

ON

Time

RST-CM

ON

Time

Start

Tripped

Related Functions: FU2-22 ~ FU2-25 [Speed Search]

Related Functions: FU2-22 ~ FU2-25 [Speed Search]

FU2

►Speed Search

22 0000

0000

22

Factory Default:

0000

0000