Chapter 5 - parameter list, 1 drive group [drv – HP 30 HP30 User Manual

Page 61

Advertising
background image

5-1

CHAPTER 5 -

PARAMETER LIST

5.1 Drive Group [DRV]

Keypad Display

Setting Range

Code

Description

LCD

7-Segment

LCD

7-Segment

Units

Factory

Default

Adj.

During

Run

Page

DRV-00

10

Command Frequency or
Command Torque
(Output Frequency/
Torque during motor run,
Reference Frequency/
Torque during motor
stop)
Output Current (LCD)

Cmd. freq

or

Cmd. Trq

F or r

(DRV-13)

0 to FU1-20 (Max. freq)

0.01

0.00 [Hz]

Yes

6-2

DRV-01 Acceleration Time

Acc. time

01

0 to 6000

0.1

10.0 [sec]

Yes

6-2

DRV-02 Deceleration Time

Dec. time

02

0 to 6000

0.1

20.0 [sec]

Yes

6-2

Keypad 0

Fx/Rx-1 1

DRV-03

Drive Mode
(Run/Stop Method)

Drive mode

03

Fx/Rx-2 2

- Fx/Rx-1 No 6-2

Keypad-1 0
Keypad-2 1

V1 2

I 3

DRV-04

Frequency Mode or
Torque Mode
(Frequency/Torque
setting Method)

Freq mode

or

Torque mode

04

V1+I 4

- Keypad-1 No 6-2

DRV-05 Step Frequency 1

Step freq-1

05

10.00 [Hz]

DRV-06 Step Frequency 2

Step freq-2

06

20.00 [Hz]

DRV-07 Step Frequency 3

Step freq-3

07

FU1-22 to FU1-20

(Starting freq to Max. freq)

0.01

30.00 [Hz]

Yes 6-2

DRV-08 Output Current

Current

08

The Load Current in RMS

-

[A]

-

6-2

DRV-09 Motor Speed

Speed

09

The Motor Speed in rpm

-

[rpm]

-

6-2

DRV-10 DC link Voltage

DC link Vtg

10

The DC Link Voltage inside inverter

-

[V]

-

6-2

DRV-11 User Display Selection

User disp

11

Selected in FU2-73 (User Disp)

-

-

-

6-2

DRV-12 Fault Display

Fault

12

- -

-

None

nOn

- 6-2

0 [Forward]

DRV-13 Motor Direction Set

Not

displayed in

LCD keypad

13

Not available

1 [reverse]

- 0 Yes

6-2

DRV-14

Target/Output Frequency
Display

TAR

OUT

14

- -

-

0.00

[Hz]

Yes

6-2

DRV-15

11

Reference/Feedback
Frequency Display

REF

FBK

15

- -

-

0.00

[Hz]

Yes

6-2

DRV-16 Speed Unit Selection

Hz/Rpm Disp

16

Hz disp

0

-

-

Yes

6-2

10

The speed unit is changed to [%] when FU2-39 is set to ‘Sensorless_T’ or ‘Vector_TRQ’.

11

Code DRV-15 appears only when FU2-47 is set to ‘Yes’.

Advertising