Chapter 6 - Parameter description [FU1]

6-10











[Accel/Decel Pattern: ‘Linear’]











[Accel/Decel Pattern: ‘S-curve’]











[Accel/Decel Pattern: ‘U-curve’]


FU1-07: Stop Mode






Sets the stopping method for the inverter.

Setting Range

LCD 7-Seg

Description

Decel

0

Inverter stops by the deceleration pattern.

Dc-brake

1

Inverter stops with DC injection braking.
Inverter outputs DC voltage when the

frequency reached the DC injection
braking frequency set in FU1-08 during
decelerating.

Free-run

(Coast to stop)

2

Inverter cuts off its output immediately
when the stop signal is commanded.

















[Stop Mode: ‘Decel’]


















[Stop Mode: ‘Dc-brake’]

Output Frequency

Time

Acc. Pattern

Dec. Pattern

Output Frequency

Time

Acc. Pattern

Dec. Pattern

Output Frequency

Time

Acc. Pattern

Dec. Pattern

FU1

► Stop mode

07 Decel

0

07

Factory Default:

Decel

0

Output Frequency

Time

FX-CM

ON

Output Voltage

Time

Time

Stop Command

Output Frequency

Time

FX-CM

ON

Output Voltage

Time

Time

Stop Command

FU1-08

FU1-10

[DCBr Value]

t1 t2

t1: FU1-09
t2: FU1-11