Chapter 6 - Parameter Description [FU2]

6-25

FU2-40

LCD display

Description

0 No

Auto-tuning

disabled

1 All

Auto-tuning all

parameters

2

Rs + Lsigma

Stator resistance (Rs) and

Leakage inductance

(Lsigma) Auto-tuning

3

Enc Test

PG status check

4 Tr

Rotor constant(Tr)

calculation

➨ Note 1 : Ls and Noload-Curr are only valid during Motor

Rotation mode.

➨ Note 2 : The motor constants values change with temperature

change, so auto tuning is to be conducted after the
temperature of the motor is stabilized.

➨ Note 3 : The auto-tuning result could be different unless CMC

motor is used.

➨ Note 4 : The actual motor parameters (Rs, Rr, Lsigma, Tr)

can be used or set by user.

Code LCD display

Name

Description

FU2-

34

Noload-Curr

No Load

Motor

Current

(RMS)

Setting and display the No
Load Motor Current
(RMS)

FU2-

40

Auto tuning Auto Tuning Auto-tuning enable

FU2-

41

Rs

Stator

resistance

Setting and display the
Stator resistance Rs

FU2-

42

Lsigma

Leakage

inductance

Setting and display the
Lsigma

FU2-

43

Ls

Stator

inductance

Setting and display the
Stator inductance Ls

FU2-

44

Tr

Rotor

constant

Setting and display the
Rotor constant Tr.


[Keypad display during Auto-tuning of motor parameters]

Display

Code

LED

7-Segment

Description

Rs Tuning

T1 Displayed

during

Stator

resistance (Rs) Auto-tuning

Lsigma

Tuning

T2

Displayed during Leakage
inductance (Lsigma) auto-
tuning.

Ls Tuning

T3 Displayed

during

Stator

inductance (Ls) and No-load
current auto-tuning.

FU2-

40

ENC Test

T4 Displayed

during

Encoder

auto-tuning.

Tr Tuning

T5

Displayed during Rotor filter
time constant (Tr) auto-
tuning

[Keypad error display after Encoder test]

Display

Code

LED

7-Segment

Description

Enc Err

T6 Displayed

when

incorrect

Encoder wiring error occurs

FU2-

40

Enc Rev

T7 Displayed

when

Encoder

wiring is connected reversly.


[Motor parameter display corresponding to inverter
capacity]

Motor parameter

Class

inverter

capacity

Rs Lsigma Ls Tr

0.8[kW] ~

5.5[kW]

X.XXX

ohm

X.XX

mH

X.XX

mH

XXX

ms

200V

7.5[kW] ~

55[kW]

X.X

mohm

X.XXX

mH

X.XX

mH

XXX

ms

0.8[kW] ~

1.5[kW]

X.XX

ohm

X.X mH X. mH

XXX

ms

2.2[kW] ~

15[kW]

X.XXX

ohm

X.XX

mH

X.X mH

XXX

ms

400V

18.5[kW] ~

75[kW]

X.X

mohm

X.XXX

mH

X.XX

XXX

ms

➨ Note : For 7-segment Keypad, parameter unit is not

displayed.










FU2-45: P Gain for Sensorless Control
FU2-46: I Gain for Sensorless Control






SL P-gain is the proportional gain of speed controller. If
this value is set high, you can get fast speed response
characteristic. However, if this value is set too high, the
steady state characteristics may become unstable.

FU2

► SL P-gain

45 32767

3276

45

Factory Default:

32767

3276

Related Functions: FU2-30~37 [Motor related parameters]

FU2-39 [Control mode selection]

EXT-01 [Sub Board Type Display]

EXT-14 [Encoder Feedback Frequency]

EXT-15 [Pulse Input Signal Selection

]