Chapter 6 - parameter description [i/o – HP 30 HP30 User Manual

Page 131

Advertising
background image

Chapter 6 - Parameter Description [I/O]

6-39

[Dc-brake]
DC Injection Braking can be activated during inverter
stopped by configuring one of the multi-function input
terminals (P1, P2, P3) to ‘Dc-bake’. To activate the DC
Injection Braking, close the contact on the assigned
terminal while the inverter is stopped.

[Exchange]
Exchange is used to bypass the motor from the inverter
line to commercial power or the opposite. To bypass the
motor to commercial line, set the ‘Exchange’ function in
multi-function output terminal and ‘INV line’, ‘COMM line’
function in multi-function output terminal. Speed search
function (FU2-22) is activated automatically during
exchanging operation.

M2

U

V

W

G

R
S
T

FX

RX

P1

P3

CM

VR

V1

I

5G

FM

5G

A

B

C

AXA

AXB

P2

MOTOR

Potentiometer

(1 kohm, 1/2W)

Speed signal Input

2

Forward Run/Stop

Reverse Run/Stop

‘Exchange’

Common Terminal

Factory Setting:
‘Speed-L’
‘Speed-M’
‘Speed-H’

Power supply for
speed signal:
+ 11V, 10mA

Speed signal input:
0 ~ 10V

Speed signal input:
4 ~20mA (250ohm)

Common for
VR, V1, I

Shield

MCCB

M1

M2

AC220V Line

M1

M1

[Wiring to By-Pass Motor to Commercial line]


























[Exchanging Sequence]


[Up, Down]
By using the Up and Down function, the drive can
accelerate to a steady speed and decelerate down to a
desired speed by using only two input terminals.













[Up/Down Operation]

P1-CM

‘Up’

ON

Output Frequency

Time

Time

P2-CM

‘Down’

ON

Time

FX-CM

ON

Time

Freq.

Max.

‘Exchange’-CM

FX-CM

ON

Output Frequency

Time

Time

ON

Time

AXA-AXC

‘COMM line’

ON

Time

M1

ON

Time

M2

ON

Time

ON

t1 t2

Inverter

Drive

Inverter

Drive

Commercial

Line Drive

t1, t2: 50msec (interlock time)

Speed Search

‘INV line’

ON

Time

ON

Advertising