Operation example (5) vector_spd control, Chapter 4 - operation examples, Operation condition – HP 30 HP30 User Manual

Page 59: Wiring

Advertising
background image

Chapter 4 - Operation Examples

4-13

Operation
Example (5)

Vector_SPD Control

[Operation condition]

-. Control Mode : Vector_SPD Control, -. Encoder specification : Pulse number (1024), Line Drive type
-. Freq command : set it 55[Hz] via KPD-1
-. Accel/Decel time : Accel – 15 [sec], Decel – 25 [sec], -. Drive mode : Run/Stop via terminal FX/RX

[Wiring]

AOC

R
S

T

G

U
V

W

B1

B2

FX
RX
BX
RST
JOG
P1
P2
P3
CM

VR
V1
5G

IM

3P

AC

Input

BOC

A+

A-

B+

B-

FBA
FBB

GND

E

Encoder

GND

+5V
+5V

VCC
VCC

Keypad

connector

MODE

PROG

ENT

REV

SHIFT

ESC

STOP

RESET

FWD

LC-200

Sub-B

Step

Parameter setting

Code

Description

1 Motor

related

setting

FU2-30 ~ FU2-

36

Set motor capacity, pole number, rated voltage/ current/slip and
efficiency.

2 Encoder

related

setting

EXT-12
EXT-15
EXT-16

Set EXT-12 to Feed-back, EXT-1 to A+B
Set EXT-16 to 1024

3

Control Mode Selection

Fu2-39

Encoder related setting should be done before setting control mode to
Vector_SPD.

4 Auto-tuning

FU2-40

Auto-tuning starts when set to ALL. Read the encode rmanual carefully
to clear the error if the messages ” Enc Err”, “Enc Rev” are displayed.

5

Keypad input setting

DRV-4
DRV-0

Set DRV-4 to KPD-1 and press the Prog key to set 55 [Hz] in Drv-0.

6

Accel/Decel time setting

DRV-1
DRV-2

Accel time: set 15[Sec]
Decel time: set 25[Sec]

7

Drive mode

DRV-3

Set it to FX/RX-1.

8 FX/RX

terminal

Motor runs with Accel time 15 [Sec] at 55 [Hz] if FX/RX terminal is
turned ON.
Motor decelerates to stop with Decel time 25 [Sec] if FX/RX terminal is
turned OFF.