Chapter 6 - Parameter description [FU1]

6-12

FU1-12: Starting DC Injection Braking Time
FU1-13: Staring DC Injection Braking Time










Inverter holds the starting frequency for Starting DC
Injection Braking Time. It outputs DC voltage to the motor
for FU1-13 [Starting DC Injection Braking Time] with the
FU1-12 [Starting DC Injection Braking Voltage] before
accelerating.

























[Starting DC Injection Braking Operation]


Note: The DC injection braking function does not function

when either FU1-12 or FU1-13 is set to “0”.

Note: FU1-12 [Starting DC Injection Braking Voltage] is

also used as the DC Injection Braking Voltage for the
multifunction input when the multifunction input is set to “DC
braking”.


FU1-14: Pre-excitation Time




To set the time for pre-exitation (Flux gain time) before
starting Vector or Sensorless Vector control

After FU1-14 [Pre-excitation Time] elapses the motor

starts acceleration,

Code

LCD display

Factory setting

Setting range

FU1-14

PreExTime

1 [sec]

0 ~ 60 [sec]






















FU1

► DcSt value

12 50 %

50

12

Factory Default:

50 %

50

FU1

► DcSt time

13 0.0 sec

0.0

13

Factory Default:

0.0 sec

0.0

Output Frequency

Time

FX-CM

ON

Output Voltage

Time

Time

Run Command

FU1-22

FU1-12

t1

t1: FU1-13 [Starting DC Injection
Braking Time]

Output Current

Time

Related Functions: FU2-33 [Rated Current of Motor]

FU2-33: the DC current is limited by this parameter.

FX-CM

Output freq

[ Hz ]

Output
voltage
[V]

T1 = Pre-excitation time

Ralated function : FU2-34 [No Load Motor Current (RMS)]

FU1-16 [Pre-excitation Current]

FU1

► PreExTime

14 1.0 sec

1.0

14

Factory Default:

1.0 sec