Chapter 6 - Parameter description [FU1]

6-18

the motor has overheated. It trips in one minute when
150% of rated motor current established in FU2-33 flows
for one minute.

Note: The set value is the percentage of FU2-33 [Rated

Motor Current].






This is the current at which the motor can run continuously.
Generally, this value is set to ‘100%’ and which means the
rated motor current set in FU2-33. This value must be set
less than FU1-52 [ETH 1min].

Note: The set value is the percentage of FU2-33 [Rated

Motor Current].










[Motor i

2

t Characteristic Curve]







To make the ETH function (Motor i

2

t) work correctly, the

motor cooling method must be selected correctly according
to the motor.

[Self-cool] is a motor that has a cooling fan connected
directly to the shaft of the motor. Cooling effects of a self-
cooled motor decrease when a motor is running at low
speeds. The motor current is derated as the motor speed
decreases.

[Forced-cool] is a motor that uses a separate motor to

power a cooling fan. As the motor speed changes, the
cooling effects doe not change.









[Load Current Derating Curve]


Note: Despite the motor current changing frequently due to

load fluctuation or acceleration and deceleration, the
inverter calculates the i

2

t

and accumulates the value to

protect the motor.




FU1-54: Overload Warning Level
FU1-55: Overload Warning Time











The inverter generates an alarm signal when the output
current has reached the FU1-54 [Overload Warning Level]
for the FU1-55 [Overload Warning Time]. The alarm signal
persists for the FU1-55 even if the current has become the
level below the FU1-54.

Multi-function output terminal (AXA-AXC) is used as the
alarm signal output. To output the alarm signal, set I/O 44
[Multifunction Auxiliary Contact Output] to ‘OL’.

Note: Inverter is not tripped by this function.

Note: The set value is the percentage of FU2-33 [Rated

FU1

► ETH cont

52 100 %

100

52

Factory Default:

100 %

100

Load Current [%]

Trip Time

FU1-51

[ETH 1min]

1 minute

FU1-52

[ETH cont]

FU1

► Motor type

53 Self-cool

0

53

Factory Default:

Self-cool

0

100%

95%

65%

Output Current

20Hz

60Hz

Self-Cool

Forced-Cool

Related Functions: FU2-33 [Rated Motor Current]

FU1

► OL level

54 150 %

150

54

Factory Default:

150 %

150

FU1

► OL time

55 10.0 sec

10.0

55

Factory Default:

10.0 sec

10.0