Chapter 4 – Function Settings

4-7

8) Operation-starting method

Parameter Name

Code

Description

Starting method

FU2-20
FU2-21
FU2-26
FU2-27

Motor starting method:
[FU2-20] : Power-on run,
[FU2-21] Restart after Fault Reset,
[FU2-26] Number of Auto Restart Attempt
[FU2-27] Delay Time Before Auto Restart
See parameter description for more.

Speed Search Selection

FU2-22
FU2-23
FU2-24
FU2-25

Speed search function is available during Accel, trip,
instant power failure, restart after fault reset and auto
restart. See parameter description for more.

4.1.3

Advanced function 2 setting

1) PID operation
The inverter can be used to exercise process control, e.g. flow rate, air volume or pressure via PID feedback control.

Parameter Name

Code

Description

PID control setting

FU2-41~ FU2-60

Setting parameters for PID control


2) Jog and Multi-speed operation

Parameter Name

Code

Description

Multi function input

terminal setting

I/O-12 ~14

EXT2 ~ 4

If I/O-12 ~14 are set to Speed-H, Speed-M, Speed-L,
multi- speed operation up to speed 7 enable..

Filter time constant for

input terminal

I/O-17

Effective for eliminating noise in the freq. setting circuit

Speed reference value

DRV-05 ~ 7

I/O-21 ~ I/O-24

Setting speed reference value for each step

Accel/Decel time

setting for each step

I/O-25 ~ 38

Setting Accel/Decel time for each step

Jog freq.

I/O-20

Setting jog freq for jog operation

Speed-H

Speed-M

Speed-L

JOG

Speed Signal

Applied speed value

0

0

0

0

Speed 0

DRV-00

X x X 1 Jog

freq.

I/O-20

0

0

1

0

Speed –1

DRV-05

0

1

0

0

Speed –2

DRV-06

0

1

1

0

Speed –3

DRV-07

1

0

0

0

Speed –4

I/O-21

1

0

1

0

Speed –5

I/O-22

1

1

0

0

Speed –6

I/O-23

1

1

1

0

Speed –7

I/O-24

Advertising