Chapter 6 - Parameter description [FU1]

6-13

FU1-15: Hold Time




To set the time to maintain holding torque at zero speed

and stop the operation in a shortest time during

Vector_SPD mode operation

The inverter runs to maintain speed 0 for the hold

time in Vector_SPD mode and decelerates to stop
after the hold time elapse.














Operation method during Hold Time:

FU1-7[Stop mode] Decel: speed zero control

FU1-7[Stop mode] DC-brake

FU1-16: Pre-excitation Current







FU1-16 [Pre-excitation Current] is applied during FU1-14.
When the motor magnetic flux increases to match the
rated magnetic flux, pre-excitation current starts to
decrease. When the motor magnetic flux reaches to the
rated magnetic flux, the pre-excitation current matches the
rated pre-excitation current.



Code

LCD display

Factory setting

Setting range

FU1-16

Flux Force

100 [%]

100 ~ 500 [%]
















FU1-20: Maximum Frequency
FU1-21: Base Frequency
FU1-22: Starting Frequency
















FU1-20 [Maximum Frequency] is the maximum output
frequency of the inverter. Make sure this maximum
frequency does not exceed the rated speed of the motor.
FU1-21 [Base Frequency] is the frequency where the
inverter outputs its rated voltage. In case of using a 50Hz
motor, set this to 50Hz.
FU1-22 [Starting Frequency] is the frequency where the
inverter starts to output its voltage.

Output
Voltage
[V]

Output Speed
[Hz or Rpm]

Hold time

FX-CM

Motor

magnetic flux

Excited current

FU1

► Max freq

20 60.00 Hz

60.00

20

Factory Default:

60.00 Hz

60.00

FU1

► Base freq

21 60.00 Hz

60.00

21

Factory Default:

60.00 Hz

60.00

FU1

► Start freq

22 0.50 Hz

0.50

22

Factory Default:

0.50 Hz

0.50

FU1

► Hold Time

15 1000 ms

1000

15

Factory Default:

1000 ms

1000

FU1

► Flux Force

16 100.0 %

1 00.0

16

Factory Default:

100.0 %

100.0

Related Functions:

FU2-34 [No Load Motor Current (RMS)]

FU1-14 [Pre-excitation Time]