Chapter 8 - Troubleshooting & Maintenance


8-9

8.6 Daily and Periodic Inspection Items

Period

In

sp

ec

tion

Lo

cat

ion

In

sp

ec

tion

Ite

m

Inspection

Dai

ly

1 y

ear

2 y

ear

Inspection Method

Criterion

Measuring

Instrument

Ambient

Environ-

ment

Is there any dust?

Is the ambient temperature and humidity

adequate?

Ο

Refer to the precautions

Temperature:

-10~+40 no

freezing.
Humidity: Under

50% no dew

Thermometer,

Hygrometer,

Recorder

Equipment Is there any abnormal oscillation or noise

Ο

Use sight and hearing

No abnormality

All

Input

Voltage

Is the input voltage of the main circuit normal

Ο

Measure the voltage between the

terminals R, S, T

Digital

Multi-

Meter/Tester

All

Megger check (between the main circuit and

the ground)
Are any fixed parts removed?

Are there any traces of overheating at each
component’s cleaning?

Ο


Ο

Ο


Ο

Undo the inverter connections short

the terminals R, S, T, U, V, W and
measure between these parts and the

ground.
Tighten the screws.

Visual check.

Over 5MΩ
No fault

DC 500V class

Megger

Conductor/

Wire

Is the conductor rusty?

Is the wire coating damaged?

Ο

Ο

Visual check

No fault

Terminal

Is there any damage?

Ο

Visual check

No fault

IGBT

Module

/Diode

Module

Check the resistance between each of the
terminals.

Ο

Undo the inverter connection and
measure the resistance between R, S,
T ⇔ P, N and U, V, W ⇔ P, N with a
tester.

(Refer ‘How to
Check Power

Components”)

Digital Multi-
Meter/Analog

Tester

Smoothing

Capacitor

Is there any liquid coming out?
Is the safety pin out, and is there any

swelling?
Measure the capacitance.

Ο



Ο


Ο

Visual

check.

Measure with a capacitance-

measuring device.

No fault
Over 85% of the

rated capacity

Capacitance
Measuring Device

Relay

Is there any chattering noise during

operation?
Is there any damage to the contact

Ο


Ο

Auditory

check.


Visual check.

No fault

M

ai

n C

ircu

it

Resistor

Is there any damage to the resistor

insulation?
Is the wiring in the resistor damaged (open)?

Ο


Ο

Visual

check.


Disconnect one of the connections

and measure with a tester.

No fault

Error must be
within ±10% the
displayed
resistance

Digital Multi-

Meter/Analog
Tester

Co

nt

ro

l Ci

rc

ui

t

Pr

ot

ec

tiv

e Ci

rc

ui

t

Operation

Check

Is there any unbalance between each

phases of the output voltage?

Nothing must be wrong with display circuit

after executing the sequence protective
operation

Ο



Ο

Measure the voltage between the

output terminals U, V and W.

Short and open the inverter protective

circuit output.

The voltage

balance between
the phases for

200V (800V) class

is under 4V (8V).
The fault circuit

operates according
to the sequence.

Digital Multi-

Meter/Rectifying
Voltmeter

C

oo

lin

g

Sy

st

em

Cooling

Fan

Is there any abnormal oscillation or noise?
Is the connection area loose?

Ο

Ο

Turn OFF the power and turn the fan
by hand.

Tighten the connections.

Must rotate
smoothly.

No fault

Di

sp

la

y

Meter

Is the displayed value correct?

Ο Ο

Check the meter reading at the
exterior of the panel

Check the
specified and

management
values.

Voltmeter/
Ammeter etc.

All

Are there any abnormal vibrations or noise?

Is there any unusual odor?

Ο

Ο

Auditory, sensory, visual check.

Check for overheat and damage.

No fault

Mot

or

Insulation

Resistor

Megger check (between the output terminals
and the ground terminal)

Ο

Undo the U, V and W connections and
tie the motor wiring.

Over 5MΩ

500V class
Megger

Note: Values in ( ) is for the 400V class inverters.