HP 30 HP30 User Manual

Page 69

Advertising
background image

Chapter 5 - Parameter List

5-9

Keypad Display

Setting Range

Code

Description

LCD

7-Segment

LCD

7-Segment

Units

Factory

Default

Adj.

During

Run

Page

FU2-72 Power On Display

PowerOn disp

72

0 to 12

1

0

Yes

6-2

Voltage 0

FU2-73 User Display Selection

User disp

73

Watt 1

- Voltage Yes

6-2

FU2-74

Gain for Motor Speed
Display

RPM factor

74

1 to 1000 [%]

1

100 [%]

Yes

6-2

None 0

Int. DB-R

1

FU2-75

DB (Dynamic Braking)
Resistor Mode Selection

DB mode

75

Ext. DB-R

2

- Int.

DB-R Yes 6-2

FU2-76

23

Duty of Dynamic Braking
Resistor

DB %ED

76

0 to 30 [%]

1

10 [%]

Yes

6-2

FU2-79 Software Version

S/W version

79

Ver 2.0

-

-

-

6-2

FU2-81

24

2

nd

Acceleration Time

2nd Acc time

81

0 to 6000 [sec]

0.1

5.0 [sec]

Yes

FU2-82 2

nd

Deceleration Time

2nd Dec time

82

0 to 6000 [sec]

0.1

10.0 [sec]

Yes

FU2-83 2

nd

Base Frequency

2nd BaseFreq

83

30 to FU1-20

0.01 60.00 [Hz]

No

Linear 0

Square 1

FU2-84 2

nd

V/F Pattern

2nd V/F

84

User V/F

2

- Linear No

FU2-85 2

nd

Forward Torque Boost 2nd F-boost

85

0 to 15 [%]

0.1

2.0 [%]

No

FU2-86

2

nd

Reverse Torque

Boost

2nd R-boost

86

0 to 15 [%]

0.1

2.0 [%]

No

FU2-87 2

nd

Stall Prevention Level

2nd Stall

87

30 to 150 [%]

1

150[ %]

No

FU2-88

2

nd

Electronic Thermal

Level for 1 minute

2nd ETH 1min

88

FU2-89 to 200 [%]

1

150 [%]

Yes

FU2-89

2

nd

Electronic Thermal

Level for continuous

2nd ETH cont

89

50 to FU2-88

(Maximum 150%)

1 100

[%] Yes

FU2-90 2

nd

Rated Motor Current

2nd R-Curr

90

1 to 200 [A]

0.1

3.6 [A]

No

6-2

No 0

FU2-91

Read Parameters into
Keypad from Inverter

Para. Read

91

Yes 1

- No No

No 0

FU2-92

Write Parameters to
Inverter from Keypad

Para. Write

92

Yes 1

- No No

6-2

No 0

All Groups

1

DRV 2

FU1 3
FU2 4

I/O 5

EXT 6

COM 7

FU2-93 Initialize Parameters

Para. Init

93

APP 8

- No No

6-2

23

Code FU2-76 appears only when FU2-75 is set to ‘Ext. DB-R’.

24

Code FU2-81 through FU2-90 appear only when one of I/O-12 ~ I/O-14 is set to ‘2nd function’.

Advertising