Chapter 1 - Installation

1-7

1.6 Basic Wiring

230/460 V
50/60 Hz

U

V

W

G ( )

R
S
T

N

1

DB Unit(Optional)

4

DB Resitor

φ

3

MCCB(OPTION)

FX

RX

BX

RST

P1

P3

CM

VR

V1

I

5G

+

FM

5G

(N.O.) A

AXA

AXB

Output Frequency Meter
(0~10V Linear)

P2

MOTOR

Potentiometer
(1 kohm, 1/2W)

Speed signal Input

2

Forward Run/Stop

Reverse Run/Stop

Inverter Disable

Fault Reset

Multi-function Input 1

Multi-function Input 2

Multi-function Input 3

Common Terminal

Factory Setting:
‘Speed-L’
‘Speed-M’
‘Speed-H’

Power supply for
speed signal:
+ 11V, 10mA

Speed signal input:
0 ~ 10V

Speed signal input:
4 ~20mA (250ohm)

Common for
VR, V1, I

Fault output relay
lless than AC250V, 1A
lless than DC30V, 1A

Multi-function output relay1
lless than AC250V, 1A
lless than DC30V, 1A
Factory setting: ‘Run’

Note) Main Circuit Terminals Control Circuit Terminals.
1. The terminal configuration varies depend on the model number. Please refer to the ‘1.7 Power terminals’.

2. Analog speed command may be set by Voltage, Current or both.
3. When installing the DC Reactor, the Common Busbar between P1 and P2 must be removed.
4. 1 ~ 10 HP inverters have on-board braking circuit. Braking resistors are only included for 1 ~ 5 inverters.

15 ~ 30 HP inverters need optional braking unit and resistor for dynamic braking.

P2

1

P1

1

DC Bus Choke (Optional)

3

FM

Dynamic

Braking Unit

(Optional)

P N B1 B2

DC Bus Choke

DB Resistor

JOG

Jog

Shield

(N.C.) B

C