Chapter 4 - Operation Examples

4-12

Operation
Example (4)

Sensorless_S Control + Multi-speed operation + Analog output (FM)

[Operation condition]

-. Control mode : Sensorless Speed control
-. Frequency command : Multi-function input from

SUB-A and 8 step speed operation

(Multi-speed 7 + jog freq 1)

-. Accel time : 5 [Sec], Decel time: 5 [Sec]
-. Drive mode : Run/Stop and speed output via terminal FX/RX

[Wiring]

I/O-20 Speed 4
I/O-21 Speed 5
I/O-22 Speed 6
I/O-23 Speed 7

Multi-speed freq setting range

DRV-00 Speed 0

DRV-05 Speed 1
DRV-06 Speed 2
DRV-07 Speed 3

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON











SPD 0 SPD 1 SPD 2 SPD 3 SPD 4 SPD 5 SPD 6 SPD 7 JOG

P4

P5

P6

JOG

FX

RX

Output freq [Hz]

Output

freq meter

0 -10 V,

Pulse

R
S
T
G

U
V

W

B1

B2

FX
RX
BX
RST

JOG

P1
P2
P3

CM

FM

5G

30C

30B

AXA
AXC

IM

S/W

P4

CN5

P5
P6

CM

Sub - A

S/W

FM

30A

Step

Parameter setting

Code

Description

1

Control Mode Selection

FU2-39

Set it to Sensorless_S.

2

Drive mode

DRV-3

Set it to FX/RX-1.

3

Multi-function input

EXT-2 ~ 4

Set P3, P4, P5 to Speed-L, Speed-M, Speed-H.

4

FM

(Frequency Meter) Output

Selection

I/O-40

Set it to Frequency output

5

FM Output Adjustment

I/O-41

Output V = 10V x output freq x output gain (ex100%) /
( Max freq x 100 )

6

Terminal FX

Motor runs in forward direction at the set freq via P3, 4, 5 if Fx terminal is
ON.
Motor decelerates to stop with Decel time 5 [sec] if FX terminal is OFF.

7

Terminal RX

Motor runs in reverse direction at the set freq via P3, 4, 5 if RX terminal is
ON.
Motor decelerates to stop with Decel time 5 [sec] if RX terminal is OFF.


Advertising