Chapter 6 - Parameter Description [I/O]

6-45

Setting Range

LCD 7-Seg

Description

Lost Command

11

Lost command detection

Run

12

Inverter running detection

Stop

13

Inverter stop detection

Steady

14

Steady speed detection

INV line

15

COMM line

16

Exchange signal outputs

Ssearch

17

Speed search mode detection

Step pulse

18

Step detection in Auto mode

Seq pulse

19

Sequence detection in Auto mode

Ready

20

Inverter ready detection

Trv. ACC

21

Traverse acceleration frequency

Trv. DEC

22

Traverse deceleration frequency

MMC

23

Used for MMC operation

Zspd Dect

24

0 Rpm detection signal during vector
control

Torq Dect

25

Torque detection signal during vector
and sensorless control.



[FDT-1]
When the output frequency reaches the reference
frequency (target frequency), AXA-AXC terminal is
CLOSED.











[AXA-AXC configured as ‘FDT-1’]



[FDT-2]
AXA-AXC is CLOSED when the reference frequency is in
I/O-43 [FDT Bandwidth] centered on I/O-42 [FDT
Frequency], and the output frequency reaches I/O-43
centered on I/O-42.

















[AXA-AXC configured as ‘FDT-2’]



[FDT-3]
AXA-AXC is CLOSED when the output frequency reaches
the band centered on the FDT frequency. The output is
OPENED when the output frequency goes outside the FDT
bandwidth centered on the FDT frequency.













[AXA-AXC configured as ‘FDT-3’]



[FDT-4]
AXA-AXC is CLOSED when the output frequency reaches
the FDT frequency. The output is OPENED when the
output frequency goes below the FDT bandwidth centered
on the FDT frequency.


AXA-AXC

CLOSED

Output Frequency

Time

Time

I/O-43 / 2

I/O-42

Reference Frequency

AXA-AXC

CLOSED

Output Frequency

Time

Time

I/O-43 / 2

Reference Frequency

AXA-AXC

ON

Output Frequency

Time

Time

I/O-43 / 2

ON

I/O-42