Chapter 6 - Parameter Description [I/O]

6-47




[OV]
AXA-AXC is CLOSED when the DC link voltage is above
the Over-voltage level.










[AXA-AXC configured as ‘OV’]


[LV]
AXA-AXC is CLOSED when the DC link voltage is below
the Low-voltage level.










[AXA-AXC configured as ‘LV’]


[OH]
AXA-AXC is CLOSED when the heat sink of the inverter is
above the reference level.

[Lost Command]
AXA-AXC is CLOSED when frequency reference is lost.




[Run]
AXA-AXC is CLOED when the inverter is running.

[Stop]
AXA-AXC is CLOED when the inverter is stopped.

[INV line, COMM line]
This function is used in conjunction with ‘Exchange’
function of multi-function input for commercial line
exchange. To use both signal of ‘INV line’ and ‘COMM line’,
the optional Sub-A or Sub-C board must be installed.























[AXA-AXC configured as ‘COMM line’ and ‘Q1’ as INV line’]





[Ssearch]
AXA-AXC is CLOSED during the inverter is speed
searching.

[Step pulse]
When Auto (Sequence) operation is selected in I/O-50,
AXA-AXC outputs pulse signals on every step.


Related Functions: FU1-59 [Stall Prevention Mode]

FU1-60 [Stall Prevention Level]

AXA-AXC

ON

DC Link Voltage

Time

Time

LV Level (200V DC or 400V DC)

AXA-AXC

ON

DC Link Voltage

Time

Time

OV Level

(380V DC or 760V DC)

Related Functions: I/O-11 [Criteria for Analog Signal Loss]

I/O-48 [Operating Method at Signal Loss]

I/O-49 [Waiting Time for Time Out]

‘Exchange’-CM

FX-CM

ON

Output Frequency

Time

Time

ON

Time

AXA-AXC

‘COMM line’

ON

Time

ON

Time

ON

t1 t2

Inverter

Drive

Inverter

Drive

Commercial

Line Drive

t1, t2: 50msec (interlock time)

Speed Search

Q1-EXTG

‘INV line’

Related Functions: I/O-12 ~ I/O-14 [Multi-function input]

-

[Exchange]

Related Functions: I/O-50 ~ I/O-84 [Auto Operation]