Chapter 6 - Parameter Description [I/O]

6-48























[AXA-AXC configured as ‘Step pulse’]


[Seq pulse]
When Auto (Sequence) operation is selected in I/O-50,
AXA-AXC outputs pulse signals on the last step.

















[AXA-AXC configured as ‘Step pulse’]


[Ready]
AXA-AXC is CLOED when the inverter is ready to run.
[Trv. ACC]
CLOSED when output frequency reaches Accel frequency.
[Trv. DEC]
CLOSED when output frequency reaches Decel frequency.
[MMC]
Automatically set to ‘MMC’ when ‘MMC’ is selected in
APP-01.
[Zspd Dect]

0 Rpm detection signal during vector control

[Torq Dect]

Torque detection signal during vector and sensorless control.

I/O-45: Fault Output Relay (30A, 30B, 30C)






This function is used to allow the fault output relay to
operate when a fault occurs. The output relay terminal is
30A, 30B, 30C where 30A-30C is a normally open contact
and 30B-30C is a normally closed contact.

Bit Setting Display

Description

0 000

Fault output relay does not
operate at ‘Low voltage’ trip.

Bit 0

(LV)

1 001

Fault output relay operates at
‘Low voltage’ trip.

0 000

Fault output relay does not
operate at any fault.

Bit 1

(Trip)

1 010

Fault output relay operates at
any fault

except ‘Low voltage’

and ‘BX’ (inverter disable) fault.

0 000

Fault output relay does not
operate regardless of the retry
number.

Bit 2

(Retry)

1 100

Fault output relay operates when
the retry number set in FU2-26
decreases to 0 by faults.

When several faults occurred at the same time, Bit 0 has

the first priority.


Output Frequency

Time

Seq# / 2F

Seq# / 1F

Seq# / 3F

1T 1S

2T

2S

3T

3S

1D

(Forward)

2D

(Forward)

3D

(Reverse)

DRV-02

AXA-AXC

‘Step pulse’

Time

ON

Minimum 100msec

I/O

► Relay mode

45 010

010

45

Factory Default:

010

010

Related Functions: DRV-12 [Fault Display]

FU2-26 [Retry number]

AXA-AXC

‘Step pulse’

P1-CM

‘SEQ-L’

ON

Output Frequency

Time

ON

Time

ON

Time

P2-CM

‘SEQ-M’

P3-CM

‘Go step’

ON

ON

ON

ON

SEQ1 / 2F

SEQ2 / 2F

SEQ1 / 1F

SEQ3 / 2F

SEQ3 / 1F

Sequence 1

Sequence 3

Sequence 2

ON

Time

ON

ON

ON

ON

Minimum 100msec

Time