UPS OPERATING INSTRUCTIONS

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

9-12

9.2.9

Using the Parallel System Remote Emergency Power-off Switch

A parallel system emergency power-off is initiated by the REPO pushbutton switch. In
an emergency, you can use this switch to control the UPM outputs. The REPO switch
de‐energizes the critical load and powers down the UPMs immediately, without
asking for verification.

The UPMs, including Bypass, remain off until restarted.

C

A

U

T

I

O

N

All power to the critical load is lost when the

REPO switch is activated in the following step. You should

use this feature only when you want to de‐energize the critical load.

NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer-supplied REPO
switch is used, it may not activate in the same manner; refer to the operating instructions provided with the
switch.

To use the REPO switch:

1.

Firmly push the red pushbutton until it locks into place. The switch latches into
the activated state.

The input, output, and bypass backfeed contactors open, the battery breaker or
disconnect is tripped, and the power module is turned off immediately, without
asking for verification.

C

A

U

T

I

O

N

DO NOT attempt to restart the system after Load Off until the cause of the shutdown has been identified and
cleared.

2.

To deactivate the REPO switch, insert the supplied key and rotate clockwise until
the red pushbutton releases. To remove the key, rotate the key back to the
vertical position.

3.

To restart the UPS after using the REPO pushbutton, follow the procedure in
paragraph 9.1.1 or 9.1.2.

NOTE Follow Lockout/Tagout (LOTO) procedures for your location. The key should not be stored in the
switch. DO NOT insert the key until the fault is resolved.

Deactivated

Unlock pushbutton to release

Activated

Pushbutton locked into place

Figure 9‐2. REPO Operation