POWER WIRING INSTALLATION NOTES

071608

C

15 of 23

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

164201603-5

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-25

14.

External overcurrent protection is not provided by this product, but is required by codes.
Refer to Table E through Table J for wiring requirements. If an output lockable disconnect
is required, it is to be supplied by the user.

15.

Table O lists the maximum rating for input circuit breakers. When wiring a single‐feed
input, the rating requirements for the input circuit breakers are superceded by the ratings
listed in Table P.

Table O. Maximum Input Circuit Breaker Ratings

UPS Model

Input Voltage Rating

% Rating

208V/220V

380V

400V

415V

480V

Powerware 9390-40/20

80%

90A

50A

50A

45A

45A

100%

70A

40A

40A

35A

35A

Powerware 9390-40/30

80%

125A

70A

70A

60A

60A

100%

100A

60A

60A

50A

45A

Powerware 9390-40/40
Powerware 9390-80/40

80%

175A

90A

90A

80A

70A

100%

150A

80A

80A

70A

60A

Powerware 9390-80/50

80%

225A

110A

110A

100A

100A

100%

175A

90A

90A

90A

80A

Powerware 9390-80/60

80%

250A

150A

125A

125A

125A

100%

200A

110A

110A

100A

90A

Powerware 9390-80/80

80%

350A

175A

175A

175A

150A

100%

300A

150A

150A

150A

125A

C

A

U

T

I

O

N

To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings from Table O
in accordance with the National Electrical Code, ANSI/NFPA 70.

16.

Source protection for the AC input to bypass should be treated as if supplying an 80 kVA
three‐phase transformer, to allow for inrush current if an IDC with a transformer is installed.
Bypass input wiring and bypass input breaker rating should be treated as if supplying an
80 kVA load, regardless of the rating of the UPS.

17.

The line‐to‐line unbalanced output capability of the UPS is limited only by the full load
per phase current values for AC output to critical load shown in Table E through Table J.
The recommended line‐to‐line load unbalance is 50% or less.