NOTE 1. All building alarm inputs require an isolated normally‐open or

normally‐closed contact or switch (rated at 24 Vdc, 20 mA minimum)
connected between the alarm input and common terminal as shown.
Building alarm inputs can be programmed for use with either normally‐open
or normally‐closed contacts. All control wiring and relay and switch contacts
are customer‐supplied.

2. The building alarms can be programmed to display the alarm functional
name.

091505

A

164201603-8

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS

MINI‐CSB INTERFACE TERMINALS

1

8

P5

BUILDING ALARM
#3

BUILDING ALARM #3 RTN

MINI‐CSB

4 of 15

BUILDING ALARM
#4

BUILDING ALARM
#5

BUILDING ALARM
#6

BUILDING ALARM #4 RTN

BUILDING ALARM #5 RTN

BUILDING ALARM #6 RTN

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-45