Chapter 7

Understanding UPS Operation

The Powerware 9390 UPS is a continuous-duty, solid‐state, transformerless (at 208,
380, 400, 414, and 480 Vac), three-phase, true online system that provides
conditioned and uninterruptible AC power to the UPS system's output. The UPS
supports process control, data processing, telecommunications/PBX, research, and
non-patient medical equipment. The Powerware 9390 UPS maintains power to the
critical loads during commercial electrical power brownout, blackout, overvoltage,
undervoltage, and out‐of‐tolerance frequency conditions.

The basic system consists of a rectifier, battery converter, inverter, monitoring/
operation control panel, integrated communication server, and digital signal processor
(DSP) logic.

In this manual, the power required by your equipment is called the critical load. The
UPS supplies the critical load with conditioned power that is synchronized with your
utility power. Figure 7‐1 shows the main elements of the UPS system.

Output

Contactor

K3

Battery

Battery

Breaker

Battery

Converter

Input

Contactor

K1

AC Input to

Rectifier/

Charger

AC Input to

Bypass

Backfeed

Protection

Contactor

K5

Power Module

Inverter

Rectifier

Digital

Metering

Static

Switch

AC Output
to Critical
Load

UPS Cabinet

Figure 7‐1. Main Elements of the UPS System

If utility power is interrupted or falls outside the parameters specified in Chapter 14,
“Product Specifications,” the UPS uses a backup battery supply to maintain power to
the critical load for a specified period of time or until the utility power returns. For
extended power outages, the UPS allows you to either transfer to an alternative
power system (such as a generator) or shut down your critical load in an orderly
manner.