3 basic system configurations, Basic system configurations – Powerware 9390 UPS 100160 kVA User Manual

Page 15

Advertising
background image

INTRODUCTION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

1-5

1.3

Basic System Configurations

The following basic UPS system configurations are possible:

S

Single module UPS and one to four battery cabinets

S

Single module UPS with UPS Sidecar (maintenance bypass or 1+1 tie
configuration) and one to four battery cabinets

S

Single module UPS, one to four battery cabinets, and an optional IDC

S

Single module UPS, one to four battery cabinets, and an optional IAC (maintenance
bypass, 1+1 tie, or 1+1 tie with maintenance bypass configuration)

S

Single module UPS, one to four battery cabinets, and an optional IAC (distribution
configuration)

S

Powerware Hot Sync parallel system with two UPS modules, one to four battery
cabinets for each UPS, and an optional module tie cabinet

-

One capacity/one redundant (1+1)

-

Two capacity (2+0)

S

Powerware Hot Sync parallel system with three UPS modules, one to four battery
cabinets for each UPS, and an optional module tie cabinet

-

Two capacity/one redundant (2+1)

-

Three capacity (3+0)

S

Powerware Hot Sync parallel system with four UPS modules, one to four battery
cabinets for each UPS, and an optional module tie cabinet

-

Three capacity/one redundant (3+1)

-

Four capacity (4+0)

S

Powerware Hot Sync parallel system with two UPS modules, one to four battery
cabinets for each UPS, an optional module tie cabinet, and an optional IDC

-

One capacity/one redundant (1+1)

-

Two capacity (2+0)

S

Powerware Hot Sync parallel system with three UPS modules, one to four battery
cabinets for each UPS, an optional module tie cabinet, and an optional IDC

-

Two capacity/one redundant (2+1)

-

Three capacity (3+0)

S

Powerware Hot Sync parallel system with four UPS modules, one to four battery
cabinets for each UPS, an optional module tie cabinet, and an optional IDC

-

Three capacity/one redundant (3+1)

-

Four capacity (4+0)

The UPS system configuration can be enhanced by adding optional accessories such
as a Remote Emergency Power-off (REPO) control, RMP, or X-Slot communication
cards.