Normal mode – rt, 2 normal mode – rt – Powerware 9390 UPS 100160 kVA User Manual

Page 55

Advertising
background image

UNDERSTANDING UPS OPERATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

7-3

7.1.2

Normal Mode – RT

Figure 7‐2 shows the path of electrical power through the UPS system when the UPS
is operating in Normal mode.

Static

Switch

K5

Rectifier

Inverter

K1

K3

Battery

Converter

Battery

Battery
Breaker

Main Power Flow

Trickle Current

Energized

De-Energized

Closed

Open

Breakers

Contactors

Static

Switch

K5

Rectifier

Inverter

K1

K3

Battery

Converter

Battery

Battery
Breaker

Main Power Flow

Trickle Current

Energized

De-Energized

Closed

Open

Breakers

Contactors

Figure 7‐2. Path of Current Through the UPS in Normal Mode – RT

During normal UPS operation, power for the system is derived from a utility input
source through the rectifier input contactor K1. The front panel displays “Normal,”
indicating the incoming power is within voltage and frequency acceptance windows.
Three-phase AC input power is converted to DC using IGBT devices to produce a
regulated DC voltage to the inverter. The battery is charged directly from the
regulated rectifier output through a buck or boost DC converter, depending on
whether the system is 208V, 380V, 400V, 415V, or 480V and the size of the battery
string attached to the unit.

The battery converter derives its input from the regulated DC output of the rectifier
and provides either a boosted or bucked regulated DC voltage charge current to the
battery. The UPS monitors the battery charge condition and reports the status on the
control panel. The battery is always connected to the UPS and ready to support the
inverter should the utility input become unavailable.

Advertising