INSTALLING OPTIONAL ACCESSORIES

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

6-7

9.

Install wiring between the SCM terminal block TB2 and the monitoring
equipment. See Figure 6‐2 for terminal assignments and Drawing 164201603-8
on page A-42 for terminal block location.

System Normal

No Redundancy

On Generator

Bypass Not Available

On Battery

UPS Alarm

On Bypass

Shutdown Imminent

TB2

Figure 6‐2. Supervisory Contact Module TB2

NOTE Supervisory contacts are rated at 2.0A at 28 Vdc or 120 Vac and 0.15A at 115 Vdc.
NOTE Supervisory contacts require an external power supply. Internal 24 Vdc is not capable of supplying
contact current.