UNDERSTANDING UPS OPERATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

7-14

An ABM charge cycle is initiated whenever one of these four conditions occurs since
the last charge cycle:

S

The batteries have rested over the maximum rest time of 672 hours.

S

Accumulated discharge time is over a maximum battery discharge time of
20 seconds.

S

Battery voltage is under the opportunity charge level of 2.1 volts/cell and the unit
has been in rest mode for longer than 240 hours.

S

An XCP command Initiate Battery Test is received.

7.3.4

Bypass

The bypass has a continuous-duty fully-rated SCR switch in the bypass circuit and a
contactor in the inverter leg. In Normal mode, the contactor connects the inverter to
the output. A backfeed contactor is also provided.

7.3.5

Batteries

The UPS operates from battery strings from 192 cells (384V nominal) to 240 cells
(380V/400V/415V/480V nominal).