POWER WIRING INSTALLATION NOTES

110106

B

10 of 23

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

164201603-5

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-20

11.

Per NEC article 300‐20(a), all three‐phase conductors must be run in the same conduit.
Neutral and ground must be run in the same conduit as the phase conductors.

12.

Conduit is sized to accommodate one neutral conductor the same size as the phase
conductor and one #8 AWG ground conductor. If two neutral conductors or an oversized
neutral conductor are to be installed, check the size of the conduit needed to
accommodate the extra wire or size and use that conduit size in place of the conduit size
listed in Table N. All Powerware 9390 products can accommodate a double size neutral.

13.

Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW‐2, TW, THW,
THHW, THW‐2.

Table N. Power Cable Conduit Requirements

UPS Model

Voltage

Terminal

Number of

Wires in
Conduit

Minimum Conduit

Trade Size (inches)

Number of

Conduits

Powerware

9390-40/20

208/220

AC

AC Input to UPS

(A, B, C, Gnd)

4

2

1

AC Input to Bypass

(A, B, C, Neut, Gnd)

5

2

1

Output

(A, B, C, Neut, Gnd)

5

2

1

DC

Battery

(Positive), (Negative), Gnd

3

1‐1/4

1

Powerware

9390-40/20

480

AC

AC Input to UPS

(A, B, C, Gnd)

4

1‐1/4

1

AC Input to Bypass

(A, B, C, Neut, Gnd)

5

1‐1/4

1

Output

(A, B, C, Neut, Gnd)

5

1‐1/4

1

DC

Battery

(Positive), (Negative), Gnd

3

1‐1/4

1

Powerware

9390-40/30

208/220

AC

AC Input to UPS

(A, B, C, Gnd)

4

2‐1/2

1

AC Input to Bypass

(A, B, C, Neut, Gnd)

5

2‐1/2

1

Output

(A, B, C, Neut, Gnd)

5

2‐1/2

1

DC

Battery

(Positive), (Negative), Gnd

3

1‐1/2

1

Powerware

9390-40/30

480

AC

AC Input to UPS

(A, B, C, Gnd)

4

1‐1/2

1

AC Input to Bypass

(A, B, C, Neut, Gnd)

5

1‐1/2

1

Output

(A, B, C, Neut, Gnd)

5

1‐1/2

1

DC

Battery

(Positive), (Negative), Gnd

3

1‐1/2

1

Advertising