Powerware 9390 UPS 100160 kVA User Manual

Page 152

Advertising
background image

2 of 2

PHYSICAL FEATURES AND REQUIREMENTS

071608

C

164201603-2

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-4

6.

The clearances required around the UPS cabinet are shown in Table B.

Table B. UPS Cabinet Clearances

From Top of Cabinet

Minimum clearance over the UPS cabinet is
457.2 mm (18 inches) for ventilation

From Front of Cabinet

914.4 mm (36 inches) working space

From Back of Cabinet

None required

From Right Side of Cabinet

None required

From Left Side of Cabinet

None required

7.

The basic environmental requirements for operation of the UPS system are:

Ambient Temperature Range:

0-40°C (32-104°F)

Recommended Operating Range: 20-25°C (68-77°F)

Maximum Relative Humidity:

95%, noncondensing

The UPS ventilation requirements are shown in Table C.

Table C. Air Conditioning or Ventilation Requirements During Full Load Operation

Ratings

Voltage

Heat Rejection

BTU/hr

 1000/hr (kg‐cal/hr)

Input

Output

20 kVA

208/220

208/220

5.9 (1.49)

20 kVA

380/400/415/480

380/400/415/480

5.5 (1.38)

30 kVA

208/220

208/220

8.9 (2.24)

30 kVA

380/400/415/480

380/400/415/480

8.2 (2.07)

40 kVA

208/220

208/220

11.8 (2.98)

40 kVA

380/400/415/480

380/400/415/480

10.9 (2.76)

50 kVA

208/220

208/220

14.8 (3.73)

50 kVA

380/400/415/480

380/400/415/480

13.7 (3.45)

60 kVA

208/220

208/220

17.7 (4.47)

60 kVA

380/400/415/480

380/400/415/480

16.4 (4.14)

80 kVA

208/220

208/220

23.6 (5.96)

80 kVA

380/400/415/480

380/400/415/480

21.9 (5.52)

Ventilation required for cooling air exhaust: approximately 472 liter/sec (1000 cfm).