Powerware 9390 UPS 100160 kVA User Manual

Page 133

Advertising
background image

RESPONDING TO SYSTEM EVENTS

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

11-7

Table 11‐2. Notices (continued)

Indication

Log*

Relay

Phone

Horn

Message

Output AC Under Voltage

1

No

No

HA

Information Only

Output AC Under Voltage OK

Off

No

No

HA

Condition Cleared

Output Under or Over Frequency

1

No

No

HA

Information Only

Output Under or Over Frequency OK

Off

No

No

HA

Condition Cleared

Rectifier Current Over 125%

1

No

No

A

Information Only

Rectifier Input Over Current

1

No

No

A

Information Only

UPS Module Off

1

No

No

A

Information Only

UPS Module Off OK

Off

No

No

A

Condition Cleared

UPS on Battery

1

No

No

A

Investigate UPS

UPS on Battery OK

Off

No

No

A

Condition Cleared

UPS on Bypass

1

No

No

A

Investigate UPS

UPS on Bypass OK

Off

No

No

A

Condition Cleared

UPS on Generator

1

No

No

A

Information Only

UPS on Generator OK

Off

No

No

A

Condition Cleared

* Log codes indicate where the UPS records the event: H = History log, HA = History and Active logs, and A = Active log only.

Table 11‐3. Status

Message

Horn

Phone

Relay

Log*

Indication

Battery Switchgear Closed

No

No

No

H

User Status

Battery Switchgear Open

No

No

No

H

User Status

Bypass Switchgear Closed

No

No

No

H

User Status

Bypass Switchgear Open

No

No

No

H

User Status

Charger Status Off

No

No

No

H

User Status

Charger Status On

No

No

No

H

User Status

Check Heatsink Temp Sensor

No

No

No

No

Service Status

Check Heatsink Temp Sensor OK

No

No

No

No

User Status

Control Power Status Off

No

No

No

No

User Status

Control Power Status On

No

No

No

No

User Status

Heatsink Overtemperature

No

No

No

No

Service Status

Heatsink Overtemperature OK

No

No

No

No

User Status

Incoming Modem Call Started

No

No

No

H

User Status

Inverter Status Off

No

No

No

No

User Status

Inverter Status On

No

No

No

No

User Status

Modem Call Completed Successfully

No

No

No

H

User Status

* Log codes indicate where the UPS records the event: H = History log, HA = History and Active logs, and A = Active log only.