INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS

7 of 15

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-48

14.

Wire the maintenance bypass auxiliary contacts as applicable. See Table AA.

Table AA. Typical Maintenance Bypass Panel Auxiliary Contact Control Wiring

TB1

9

10

MAINTENANCE BYPASS PANEL

(PROVIDED BY OTHERS)

UPS

NOTE: REFER TO THE INSTRUCTIONS
PROVIDED WITH THE MAINTENANCE
BYPASS PANEL FOR WIRING INSTRUCTIONS.

MBP
AUX 1

N. O.

COMMON

(THIS EXAMPLE SHOWS CONNECTION TO BLDG ALARM 1.)

AUX CONTACT RATING

Refer to the instructions provided with the maintenance bypass panel
for auxiliary contact ratings.

Minimum Wire Size: 22 AWG