INSTALLING OPTIONAL ACCESSORIES

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

6-5

9.

Contact your Eaton service representative for verification and testing of the RIM
and its connections prior to making connections with J1 through J4 (see
Table 6‐1 and Drawing 164201603-12 on page A-63).

You can order interface cables separately for connecting to the 15‐Pin D‐Sub
Connectors.

Table 6‐1. J1 through J4 Interface Connectors

Status

J1 through J4

Description

UPS
AVAILABLE

Pins 1 and 12

Contacts are open when the UPS is offline.
Contacts are closed when the UPS is operating in Normal mode or
ready to supply the load.

UPS OFFLINE

Pins 3 and 13

Contacts are open when the UPS is offline.
Contacts are closed when the UPS is operating in Normal mode or
ready to supply the load.

BATTERY
WEAK

Pins 5 and 14

Contacts are closed when approximately two minutes of battery
time is remaining, before the critical load is lost.

UTILITY
FAILURE

Pins 6 and 15

Contacts are closed when Utility Failure is detected.