OPTIONAL REMOTE EMERGENCY
POWER‐OFF

071608

B

164201603-10

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

NOTE 1. Conduit and wiring between the

Remote Emergency Power‐off (REPO)
and the UPS to be supplied by the
customer.

2. Maximum distance between the
Remote EPO and the UPS not to exceed
500 feet.

3. Maximum wire size #14 AWG.
Minimum wire size #22 AWG.

Dimensions are in millimeters [inches]

NOTE Interface wiring and conduit between the REPO switch
and the UPS are to be supplied by the customer.

115.8
[4.56]

114.3
[4.50]

0.87

[0.22]

88.9

[3.50]

95.3

[3.57]

KNOCKOUT PATTERN
TYPICAL 5 SIDES

Front View

1.57

[0.40]

NEEDED

TO

REMOVE

KEY

Contact Block (Back View, Faceplate Removed)

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com