UPS SYSTEM ONELINE DRAWING

091505

A

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

MAINTENANCE
BYPASS PANEL

(PROVIDED BY OTHERS)

Output
from
UPS

MIB

To UPS
Input

MIB:

MAINTENANCE ISOLATION BREAKER

MBP:

MAINTENANCE BYPASS BREAKER

MBP

Backfeed

K5

K3

STATIC

SWITCH

AC INPUT

BATTERY

BREAKER

TYPICAL MAINTENANCE BYPASS PANEL POWER FLOW

BATTERY CABINET

UPS

164201603-4

CRITICAL LOAD

DISTRIBUTION

UNIT

NOTE If installing, as part of the UPS system, a maintenance bypass without a rectifier input

breaker, a minimum of two separate feeds with upstream feeder breakers, or one feed
with two upstream feeder breakers, must be provided: one for the UPS and one for
the maintenance bypass input. DO NOT use one feed or a single‐feeder breaker to
supply both the UPS and the maintenance bypass.

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-7