POWER WIRING INSTALLATION NOTES

071608

C

NOTE Customer ground can be run in any conduit listed in Table N.

8 of 23

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

164201603-5

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-18

Table L. UPS Cabinet Power Cable Terminations for the Powerware 9390-40/20,
9390-40/30, and 9390-40/40 (208V/220V Input and 208V/220V Output and
380V/400V/415V/480V Input and 380V/400V/415V/480V Output)

Terminal Function

Terminal Function

Size of Pressure

Termination

Tightening

Torque

Nm (lb in)

Type

Screw

AC Input to UPS Rectifier
and Bypass
(Single Input)

E6

Phase A

1 - #14-2/0

13.5 (120)

3/16 in. Hex

E7

Phase B

1 - #14-2/0

13.5 (120)

3/16 in. Hex

E8

Phase C

1 - #14-2/0

13.5 (120)

3/16 in. Hex

AC Input to UPS Rectifier
(Dual Input)

E1

Phase A

1 - #14-2/0

13.5 (120)

3/16 in. Hex

E2

Phase B

1 - #14-2/0

13.5 (120)

3/16 in. Hex

E3

Phase C

1 - #14-2/0

13.5 (120)

3/16 in. Hex

AC Input To Bypass
(Dual Input)

E6

Phase A

1 - #14-2/0

13.5 (120)

3/16 in. Hex

E7

Phase B

1 - #14-2/0

13.5 (120)

3/16 in. Hex

E8

Phase C

1 - #14-2/0

13.5 (120)

3/16 in. Hex

Single‐Feed To Dual‐Feed
Remove Jumpers between
Rectifier Input Terminals
and Bypass Input
Terminals

Phase A

N/A

5.6 (50)

1/4–20 Hex Nut

Phase B

N/A

5.6 (50)

1/4–20 Hex Nut

Phase C

N/A

5.6 (50)

1/4–20 Hex Nut

AC Output to
Critical Load

E9

Phase A

1 - #14-2/0

13.5 (120)

3/16 in. Hex

E10

Phase B

1 - #14-2/0

13.5 (120)

3/16 in. Hex

E11

Phase C

1 - #14-2/0

13.5 (120)

3/16 in. Hex

DC Input from
Battery to UPS

E4

Positive

1 - #14-2/0

13.5 (120)

3/16 in. Hex

E5

Negative

1 - #14-2/0

13.5 (120)

3/16 in. Hex

Input and Output Neutral

E12

Neutral

4 - #14-1/0

5.6 (50)

Slotted

Customer Ground

Ground

Ground

8 - #14-1/0

5.6 (50)

Slotted