Ups system output, Environmental, Multiple module parallel specifications – Powerware 9390 UPS 100160 kVA User Manual

Page 144: Upm input, Upm output, Battery, Module tie cabinet input, Module tie cabinet output, 2 ups system output, 3 environmental

Advertising
background image

PRODUCT SPECIFICATIONS

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

14-2

14.2.2

UPS System Output

UPS Output Capacity

100% rated current

Output Voltage Regulation



1% (10% to 100% load)

Output Voltage Adjustment
(Nominal +/–3%)

208 Vac nominal, adjustable from 202 Vac to 214 Vac
220 Vac nominal, adjustable from 214 Vac to 226 Vac
380 Vac nominal, adjustable from 369 Vac to 392 Vac
400 Vac nominal, adjustable from 388 Vac to 412 Vac
415 Vac nominal, adjustable from 403 Vac to 428 Vac
480 Vac nominal, adjustable from 466 Vac to 494 Vac

Output Voltage Harmonic
Content

1.5% max THD (linear load)
5% max THD (nonlinear load)

Output Current

See Appendix A, Table G through Table I.

Output Voltage Balance

3% for 100% maximum load imbalance (linear load)

Output Voltage Phase
Displacement

3° for 100% maximum load imbalance (linear load)

Output Transients

"5% for 100% load step or removal

Frequency Regulation

"0.01 Hz free running

Synchronous to Bypass

Bypass within voltage limits of +5%, –8% of output setting; bypass
within

"0.5 Hz

Frequency Slew Rate

1 Hz per second maximum

Overload Current Capability

102% for 10 minutes 100–101.9%
110% for 30 seconds 102–109.9%
125% for 10 seconds 110–124.9%
>125% for 10 cycles

14.2.3

Environmental

Operating Temperature

0 to 40°C (32–104°F) without derating, excluding batteries. The
recommended operating temperature is 25°C (77°F).

Operating Altitude

Maximum 1500m (5000 ft) at 40°C without derating

Storage Temperature

–25 to +60°C, excluding batteries (prolonged storage above 40°C
causes rapid battery self‐discharge)

Relative Humidity (operating
and storage)

5% to 95% maximum noncondensing

Acoustical Noise

65 dB at a 1m distance, c weighted

EMI Suppression

EN62040-2:2006 CATC3

Electrostatic Discharge (ESD)
Immunity

Meets IEC 801‐2 specifications. Withstands up to 25 kV pulse without
damage and with no disturbance or adverse effect to the critical load.