14.3

Multiple Module Parallel Specifications

14.3.1

UPM Input

Same as single module (para 14.2.1).

14.3.2

UPM Output

Same as single module (para 14.2.2).

14.3.3

Environmental

Same as single module (para 14.2.3).

14.3.4

Module Tie Cabinet Input

Operating Input Voltage
(UPM Dependent)

208 Vac for operation from 177 Vac to 229 Vac
220 Vac for operation from 187 Vac to 242 Vac
380 Vac for operation from 323 Vac to 418 Vac
400 Vac for operation from 340 Vac to 440 Vac
415 Vac for operation from 353 Vac to 457 Vac
480 Vac for operation from 408 Vac to 528 Vac

Operating Input Current

See Appendix A, Table S through Table V.

14.3.5

Module Tie Cabinet Output

Operating Output Voltage
(UPM Dependent)

208 Vac nominal, adjustable from 202 Vac to 214 Vac
220 Vac nominal, adjustable from 214 Vac to 226 Vac
380 Vac nominal, adjustable from 369 Vac to 392 Vac
400 Vac nominal, adjustable from 388 Vac to 412 Vac
415 Vac nominal, adjustable from 403 Vac to 428 Vac
480 Vac nominal, adjustable from 466 Vac to 494 Vac

Operating Output Current

See Appendix A, Table S through Table V.