9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

12-1

Chapter 12

Communication

This chapter describes the communication features of the Powerware 9390
20–80 kVA UPS and provides information about connecting hardware and using
Terminal mode.

12.1

X-Slot Cards

The Powerware 9390 UPS has two standard, factory‐installed X-Slot communication
bays with two slots each. See Drawing 164201603-8 starting on page A-42 for bay
locations. The UPS is compatible with the following X-Slot cards (see Figure 12‐1):

S

Power Xpert

®

Gateway Card - provides a data gateway from the UPS to the Power

Xpert Software; provides remote monitoring through a Web browser interface,
e-mail, and a network managment system using SNMP; connects to a twisted-pair
Ethernet (10/100BaseT) network. Modbus TCP support provides direct integration
of the UPS's parameters to a Building Management System (BMS). It has a built-in
switching hub that allows a second network device to be connected to the
network without the requirement of an additional network drop.

S

ConnectUPS-X Web/SNMP Card - has SNMP and HTTP capabilities as well as
monitoring through a Web browser interface; connects to a twisted-pair Ethernet
(10/100BaseT) network. It has a built-in switching hub that allows three additional
network devices to be connected to the network without the requirement of
additional network drops. In addition, a Powerware Environmental Monitoring
Probe (EMP) can be attached to obtain humidity, temperature, smoke alarm, and
security information.

S

Relay Interface Card (AS/400) - has isolated dry contact (Form-C) relay outputs for
UPS status: Utility failure, Low battery, UPS alarm/OK, or On bypass when
interfacing with IBM

®

AS/400 computers, other relay connected computers, and

industrial applications.

S

Modbus Card - provides direct integration of UPS information (meters and status) to
a BMS using the Modbus RTU protocol.

S

Multi-Server Card - has six serial communication ports that can communicate
simultaneously with other computers using Powerware LanSafe

®

Power

Management Software (provided on the Software Suite CD).

NOTE The Modem Card cannot be installed in X-Slot 2.

S

Modem Card - provides out-of-band remote notification and monitoring using
modem communication directly to cell phones and pagers.

S

Single-Port Card - provides serial communication.

LAN and telephone drops for use with X-Slot cards must be provided by facility
planners or the customer.

For installation and setup of an X-Slot card, please contact Eaton (see page 1-7). Refer
to the manual supplied with the X-Slot card for user instructions.