29.

See Drawing 164201603-7 for UPM terminal locations and Table K, Table L, or Table M for
termination requirements.

30.

Setup of the CAN Bridge card for parallel operation must be performed by an authorized
Eaton Customer Service Engineer

. Contact service to schedule a date.

31.

For parallel system circuit breaker ratings, see appropriate information in Table R.

32.

For parallel system ratings, see the appropriate information in Table S through Table V.

Table R. Recommended UPM Output (MOB), Main Output (MIS), and Bypass (MBP)

Circuit Breaker Ratings

UPM

Model

Configuration

Output Voltage

208V/220V

380V/400V/415V

480V

MOB

MIS

MBP

MOB

MIS

MBP

MOB

MIS

MBP

9390-40/20
9390-40/30
9390-40/40
9390-80/40

1+1

150

150

150

90

90

90

70

70

70

2+0 and 2+1

150

300

300

90

200

200

70

150

150

3+0 and 3+1

150

450

450

90

300

300

70

200

200

4+0

150

600

600

90

400

400

70

250

250

9390-80/50

1+1

200

200

200

110

110

110

80

80

80

2+0 and 2+1

200

350

350

110

225

225

80

175

175

3+0 and 3+1

200

600

600

110

350

350

80

250

250

4+0

200

700

700

110

450

450

80

350

350

9390-80/60

1+1

225

225

225

125

125

125

100

100

100

2+0 and 2+1

225

500

500

125

250

250

100

200

200

3+0 and 3+1

225

700

700

125

400

400

100

300

300

4+0

225

1000

1000

125

500

500

100

400

400

9390-80/80

1+1

300

300

300

150

150

150

125

125

125

2+0 and 2+1

300

600

600

150

300

300

125

250

250

3+0 and 3+1

300

1000

1000

150

450

450

125

400

400

4+0

300

1200

1200

150

600

600

125

500

500

Advertising