USING THE CONTROL PANEL

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

8-18

Press the LOG pushbutton on the Maximum Current Log Summary Menu bar to
display the Maximum Current Log screen.

The Maximum Current Log screen displays the individual log entries, including the
interval date and time frame, the maximum percent of full load during the interval, the
total time over limit during the interval, and the number of times over during the
interval. If the individual phase option is selected, the phases that exceeded the limit
will also be displayed. If no events have occurred, the screen will display LOG
EMPTY. Figure 8‐22 and Figure 8‐23 show the Maximum Current Log screens.

To scroll through the individual events, press the or pushbuttons on the menu
bar. To return to the Maximum Current Log Summary screen, press the SUMMARY
pushbutton on the menu bar.

To clear the Maximum Current Log, press the RESET pushbutton on the menu bar.

MAXIMUM CURRENT LOG

SUMMARY

INTERVAL : 07/30/2005

TIME OVER LIMIT

15 : 26 : 10 – 15 : 30 : 10

*** . ** %

2 MINUTES

3

RESET

MAXIMUM CURRENT EVENT

NUM TIMES OVER THIS INTERVAL

2/ 5

MAXIMUM % OF FULL LOAD

Figure 8‐22. Maximum Current Log Screen (Three-Phase Measurement)

MAXIMUM CURRENT LOG

SUMMARY

INTERVAL : 07/30/2005

TIME OVER LIMIT

15 : 26 : 10 – 15 : 30 : 10

*** . ** %

2 MINUTES

3

RESET

MAXIMUM CURRENT EVENT

NUM TIMES OVER THIS INTERVAL

2/ 5

MAXIMUM % OF FULL LOAD

PHASES OVER THIS INTERVAL

1 2

Figure 8‐23. Maximum Current Log Screen (Individual Phase Measurement)