INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS

8 of 15

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-49

15.

120 Vac should be provided from the critical bus by facility planners or the customer. See
Table AB.

Table AB. Typical Maintenance Bypass Panel Key Switch Control Wiring

Neutral

Key

Switch

Lamp

120 VAC

Fused

TB2

Output

Contactor

K3

9

10

Solenoid

MAINTENANCE BYPASS PANEL

(PROVIDED BY OTHERS)

UPS

NOTE: THE RED OK TO GO TO
MAINTENANCE BYPASS
ILLUMINATES ONLY WHEN THE
UPS MODULE IS NOT ONLINE (K3
OUTPUT CONTACTOR IS OPEN).

K3 AUX CONTACT RATING

Switched Voltage:

120 Vac at 6A Maximum
240 Vac at 4A Maximum
24 Vdc at 6A Maximum

Minimum Wire Size: 22 AWG