Through table v – Powerware 9390 UPS 100160 kVA User Manual

Page 179

Advertising
background image

POWER WIRING INSTALLATION NOTES

071608

D

21 of 23

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

164201603-5

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-31

Table U. INPUT/OUTPUT Ratings for Powerware 9390-80/60 Parallel System

Configu­

ration

Units

Rating 50/60 Hz

Basic Unit Rating at 0.9 lagging pF load

kVA

kW

60
54

60
54

60
54

60
54

60
54

Input and Bypass Input
Output

VOLTS
VOLTS

208/220
208/220

380
380

400
400

415
415

480
480

All

AC Input from UPM

Full Load Current for each Module
(3) Phases, (1) Neutral, (1) Ground

D

Amps

167/158

92

87

84

73

Minimum Conductor Size for each Module
Number per Phase for each Module

AWG or kcmil

(each)

See Table G through Table J for wire

size.

1+1

AC Input to Tie Cabinet Bypass (optional)

Full Load Current

(3) Phases, (1) Neutral-if required, (1) Ground

F

Amps

167/158

92

87

84

73

AC Output to Critical Load

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

G

Amps

167/158

92

87

84

73

System Neutral Bonding Jumper

Minimum Conductor Size
Number (See Note 28)

-

AWG or kcmil

(each)

2

(1)

6

(1)

6

(1)

6

(1)

6

(1)

2+0

and

2+1

AC Input to Tie Cabinet Bypass (optional)

Full Load Current

(3) Phases, (1) Neutral-if required, (1) Ground

F

Amps

334/316

184

174

168

146

AC Output to Critical Load

Full Load Current

(3) Phases, (1) Neutral, (1) Ground

G

Amps

334/316

184

174

168

146

System Neutral Bonding Jumper

Minimum Conductor Size
Number (See Note 28)

-

AWG or kcmil

(each)

1/0

(1)

4

(1)

4

(1)

4

(1)

4

(1)

3+0

and

3+1

AC Input to Tie Cabinet Bypass (optional)

Full Load Current

(3) Phases, (1) Neutral-if required, (1) Ground

F

Amps

501/474

276

261

252

219

AC Output to Critical Load

Full Load Current

(3) Phases, (1) Neutral, (1) Ground

G

Amps

501/474

276

261

252

219

System Neutral Bonding Jumper

Minimum Conductor Size
Number (See Note 28)

-

AWG or kcmil

(each)

2/0

(1)

1/0

(1)

1/0

(1)

1/0

(1)

2

(1)

4+0

AC Input to Tie Cabinet Bypass (optional)

Full Load Current

(3) Phases, (1) Neutral-if required, (1) Ground

F

Amps

668/632

368

348

336

292

AC Output to Critical Load

Full Load Current

(3) Phases, (1) Neutral, (1) Ground

G

Amps

668/632

368

348

336

292

System Neutral Bonding Jumper

Minimum Conductor Size
Number

(See Note 28)

-

AWG or kcmil

(each)

3/0

(1)

1/0

(1)

1/0

(1)

1/0

(1)

1/0

(1)

NOTE Callout letters

D

,

F

, and

G

map to Drawing 164201603-4, sheets 3 of 5, 4 of 5,

and 5 of 5.

Advertising