POWER WIRING INSTALLATION NOTES

110106

B

NOTE Customer ground can be run in any conduit listed in Table N.

7 of 23

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

164201603-5

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-17

10.

Terminals are UL and CSA rated at 90°C. Refer to Table K through Table M for power cable
terminations, and Table N for conduit requirements. Drawing 164201603-7 shows the
location of the power cable terminals inside the UPS cabinet.

Table K. UPS Cabinet Power Cable Terminations for the Powerware 9390-80/40,
9390-80/50, 9390-80/60, and 9390-80/80 (208V/220V Input and 208V/220V Output)

Terminal Function

Terminal Function

Size of Pressure

Termination

Tightening

Torque

Nm (lb in)

Type

Screw

AC Input to UPS Rectifier
and Bypass
(Single Input)

E6

Phase A

2 - #6-250 kcmil

42.4 (375)

5/16 in. Hex

E7

Phase B

2 - #6-250 kcmil

42.4 (375)

5/16 in. Hex

E8

Phase C

2 - #6-250 kcmil

42.4 (375)

5/16 in. Hex

AC Input to UPS Rectifier
(Dual Input)

E1

Phase A

2 - #6-250 kcmil

42.4 (375)

5/16 in. Hex

E2

Phase B

2 - #6-250 kcmil

42.4 (375)

5/16 in. Hex

E3

Phase C

2 - #6-250 kcmil

42.4 (375)

5/16 in. Hex

AC Input To Bypass
(Dual Input)

E6

Phase A

2 - #6-250 kcmil

42.4 (375)

5/16 in. Hex

E7

Phase B

2 - #6-250 kcmil

42.4 (375)

5/16 in. Hex

E8

Phase C

2 - #6-250 kcmil

42.4 (375)

5/16 in. Hex

Single‐Feed To Dual‐Feed
Remove Jumpers between
Rectifier Input Terminals
and Bypass Input
Terminals

Rectifier

Phase A

N/A

12.5 (110)

M8 Hex Bolt

Bypass

Phase A

N/A

22.6 (200)

M10 Hex Bolt

Rectifier

Phase B

N/A

12.5 (110)

M8 Hex Bolt

Bypass

Phase B

N/A

22.6 (200)

M10 Hex Bolt

Rectifier

Phase C

N/A

12.5 (110)

M8 Hex Bolt

Bypass

Phase C

N/A

22.6 (200)

M10 Hex Bolt

AC Output to
Critical Load

E9

Phase A

2 - #6-250 kcmil

42.4 (375)

5/16 in. Hex

E10

Phase B

2 - #6-250 kcmil

42.4 (375)

5/16 in. Hex

E11

Phase C

2 - #6-250 kcmil

42.4 (375)

5/16 in. Hex

DC Input from
Battery to UPS

E4

Positive

1 - #6-350 kcmil

31.1 (275)

5/16 in. Hex

E5

Negative

1 - #6-350 kcmil

31.1 (275)

5/16 in. Hex

Input and Output Neutral

E12

Neutral

8 - #2-600 kcmil

56.5 (500)

1/2 in. Hex

Customer Ground

Ground

Ground

8 - #14-1/0

5.6 (50)

Slotted